Plan Review Notes For Permit 21091113 |
Permit Number |
21091113 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-10-20 14:03:56 | 1) PLEASE PROVIDE THE SPECIFICATIONS FOR THE EXHAUST | | FANS ON THE MECHANICAL DRAWINGS. PLEASE SHOW THE | | REQUIRED CFM OF EXHAUST PER WATER CLOSET PER FBC M | | TABLE 403.3.1.1 | | 2) PLEASE SHOW THAT THE NEW BATH EXHAUST FANS | | TERMINATION LOCATION MEETS THE 3 FT. FROM OPERABLE | | OPENINGS INTO THE BUILDING PER FBC M 501.3.1-3 | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|