Plan Review Notes
Plan Review Notes For Permit 21091113
Permit Number 21091113
Review Stop M
Sequence Number 1
Notes
Date Text
2021-10-20 14:03:561) PLEASE PROVIDE THE SPECIFICATIONS FOR THE EXHAUST
 FANS ON THE MECHANICAL DRAWINGS. PLEASE SHOW THE
 REQUIRED CFM OF EXHAUST PER WATER CLOSET PER FBC M
 TABLE 403.3.1.1
 2) PLEASE SHOW THAT THE NEW BATH EXHAUST FANS
 TERMINATION LOCATION MEETS THE 3 FT. FROM OPERABLE
 OPENINGS INTO THE BUILDING PER FBC M 501.3.1-3
  