2021-11-10 09:28:45 | REST ROOM ALTERATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| 1) PLEASE SHOW BUILDING CONSTRUCTION TYPE - FBC 602.1 |
| |
| 2) PLEASE SHOW THE WIND DESIGN DATA - FBC 1603.1.4 |
| |
| 3) PLEASE SHOW THE EXTERIOR DOOR OPENING REQUIRED WIND |
| DESIGN PRESSURES - FBC 1603.1.4 |
| |
| 4) PLEASE PROVIDE A COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVAL - ALL PRODUCT APPROVALS NEED TO BE |
| REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD |
| - FBC WPB 107.3.4 |
| |
| 5) PLEASE SHOW THE EXTERIOR WALL MOISTURE BARRIER - FBC |
| 1403.2 |
| |
| 6) PLEASE SHOW THE WALL FINISH AT THE MOP SINK TO |
| COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR |
| STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS |
| SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE) |
| |
| 7) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET REAR |
| GRAB BAR LOCATION DIMENSIONS FROM THE CENTER LINE OF |
| THE TOILET - 604.5.2 REAR WALL. |
| THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| |
| 8) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER |
| HOLDER LOCATION DIMENSION FROM THE FACE OF THE TOILET |
| TO COMPLY WITH FBC 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. |
| |