Plan Review Notes
Plan Review Notes For Permit 21091039
Permit Number 21091039
Review Stop Z
Sequence Number 2
Notes
Date Text
2022-04-26 14:12:55INSUFFICIENT
  
 1) THE UNDERGROUND POWER CONDUIT RUN MUST BE INCLUDED
 WITH THIS WIRELESS COMMUNICATION FACILITY PLACEMENT
 PERMIT - RIGHT-OF-WAY SO THAT STAFF CAN VERIFY THAT THE
 UNDERGROUND POWER IS LOCATED WITHIN A RIGHT-OF-WAY AND
 DOES NOT INTERFERE WITH ANY RIGHT-OF-WAY LANDSCAPE OR
 EXISTING UTILITIES. ALL HANDHOLES AND BORE PITS MUST BE
 SHOWN.
  
 2) THE SURVEY SHOWS A 36-FOOT TALL UTILITY POLE ACROSS
 THE STREET FROM THE PROPOSED LOCATION TO SET THE
 FACILITY HEIGHT. SHEET 06 SHOWS A 40.5-FOOT-TALL
 FACILITY, WHICH EXCEEDS THE CODE PERMITTED HEIGHT
 ALLOWANCE.
  
 3) THE POLE STYLE MEETS CITY REQUIREMENTS. THE POLE
 COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP 7042 TRAFFIC
 GREY A.
  