Plan Review Notes For Permit 21091039 |
Permit Number |
21091039 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-11-29 17:32:14 | FAILED | | | | 1)THE SIDEWALK IS SHOW AS 5 FEET IN WIDTH ON THE | | ENGINEERING PLAN. THE POLE BASE IS SHOWN AS 1.5 FEET IN | | WIDTH (NOTE THERE IS A BASE PLATE THAT IS NOT | | DIMENSIONED, BUT WIDER THAN THE POLE BASE). THE SURVEY | | SHOWS THE OFFSET FROM THE PROPERTY LINE AT 0.5 FEET. | | THE MATH DOES NOT WORK TO RESULT IN 4 FEET BETWEEN THE | | POLE AND THE EDGE OF THE SIDEWALK SHOWN ON THE | | ENGINEERING PLAN. 5 FEET MINUS 1.5 FEET MINUS 0.5 FEET | | EQUALS 3 FEET BETWEEN THE POLE AND THE EDGE OF | | PAVEMENT. SURVEY AND PLAN NEED TO SHOW THE SAME | | CONDITIONS. | | | | 2) THE SECTION DRAWING IMPLIES THAT THE BASE OF THE | | POLE WILL BE ON THE RIGHT-OF-WAY LINE, WHICH WOULD | | STILL LEAVE ONLY 3.5 FEET BETWEEN THE POLE BASE AND THE | | EDGE OF THE SIDEWALK. PLEASE NOTE THAT THE BASE PLATE | | MAY NOT BE ON PRIVATE PROPERTY, SO THERE IS AN OFF-SET | | FROM THE POLE BASE REQUIRED IF THE BASE PLATE IS ON THE | | RIGHT-OF-WAY LINE. PROVIDE THE BASE PLATE DIMENSION SO | | STAFF CAN VERIFY. | | | | 3) THE POLE COMPLIES WITH THE CITY'S CONCEALMENT | | REQUIREMENTS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | [email protected] |
|