Plan Review Notes
Plan Review Notes For Permit 21091035
Permit Number 21091035
Review Stop P
Sequence Number 1
Notes
Date Text
2021-11-03 15:10:4711/03/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A-2;
  
 A. WOULD YOU PLEASE PROVIDE THE TABLE USED AND
 CALCULATION OF THE SQUARE FOOTAGE CONVERTED TO GALLONS
 PER MINUTES PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WHERE IS THE STORM WATER DARING TO. WOULD YOU PLEASE
 SHOW ON THE CIVIL DRAWINGS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. ON CORE PLAN ONE AND TWO WOULD YOU PLEASE SHOW THE
 CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORY, TURNING
 RADIUS AND TOILET PER THE 2020 FBC ACC SEC. 606.2. 2
 CLEAR FLOOR SPACE.
  
 2. ON SHEET P-1;
  
 A. THERE ARE RAIN WATER LEADER SHOWN FOR THE STORM.
 WOULD PLEASE PROVIDE AN ISOMETRIC WITH SIZE OF PIPES
 AND THE SIZE OF ROOF DRAINS PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 C. ON THE ISOMETRIC THERE IS NO MAIN SHUT-OFF INTO THE
 STRUCTURE. WOULD YOU PLEASE PROVIDE PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING
 THROUGH RATED WALLS. PLEASE SUBMIT THE COMPLETE
 ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB AMENDMENTS
 TO FBC SEC. 107.2.1
  
 3. ON SHEET IR-1; UNDER BACKFLOW A PRESSURE VACUUM
 BREAKER SHOWN BUT THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT AND THEIR CROSS CONNECTION PROGRAM ONLY
 ALLOW A REDUCED ZONE PRESSURE VACUUM BREAKER. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 4. ON SHEET IR-2;
  
 A. THE IRRIGATION HAS A PRESSURE VACUUM BREAKER SHOWN
 BUT THE CITY OF WEST PALM BEACH UTILITIES DEPARTMENT
 AND THEIR CROSS CONNECTION PROGRAM ONLY ALLOW A REDUCED
 ZONE PRESSURE VACUUM BREAKER. WOULD YOU PLEASE CORRECT
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. THE RZP WILL REQUIRE A SEPARATE PERMIT BY A LICENSED
 CONTRACTOR AND CERTIFIED BY THE CITY OF WEST PALM BEACH
 UTILITIES DEPARTMENT. WOULD YOU PLEASE ADD THIS ON THE
 PAGE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  