2021-11-03 15:10:47 | 11/03/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET A-2; |
| |
| A. WOULD YOU PLEASE PROVIDE THE TABLE USED AND |
| CALCULATION OF THE SQUARE FOOTAGE CONVERTED TO GALLONS |
| PER MINUTES PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| B. WHERE IS THE STORM WATER DARING TO. WOULD YOU PLEASE |
| SHOW ON THE CIVIL DRAWINGS PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| C. ON CORE PLAN ONE AND TWO WOULD YOU PLEASE SHOW THE |
| CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORY, TURNING |
| RADIUS AND TOILET PER THE 2020 FBC ACC SEC. 606.2. 2 |
| CLEAR FLOOR SPACE. |
| |
| 2. ON SHEET P-1; |
| |
| A. THERE ARE RAIN WATER LEADER SHOWN FOR THE STORM. |
| WOULD PLEASE PROVIDE AN ISOMETRIC WITH SIZE OF PIPES |
| AND THE SIZE OF ROOF DRAINS PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| |
| B. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| SHALL BE NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| 310.3. PLEASE MAKE A NOTE ON THIS SHEET. |
| |
| C. ON THE ISOMETRIC THERE IS NO MAIN SHUT-OFF INTO THE |
| STRUCTURE. WOULD YOU PLEASE PROVIDE PER THE WPB |
| AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS? |
| |
| D. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING |
| THROUGH RATED WALLS. PLEASE SUBMIT THE COMPLETE |
| ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB AMENDMENTS |
| TO FBC SEC. 107.2.1 |
| |
| 3. ON SHEET IR-1; UNDER BACKFLOW A PRESSURE VACUUM |
| BREAKER SHOWN BUT THE CITY OF WEST PALM BEACH UTILITIES |
| DEPARTMENT AND THEIR CROSS CONNECTION PROGRAM ONLY |
| ALLOW A REDUCED ZONE PRESSURE VACUUM BREAKER. WOULD YOU |
| PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| |
| 4. ON SHEET IR-2; |
| |
| A. THE IRRIGATION HAS A PRESSURE VACUUM BREAKER SHOWN |
| BUT THE CITY OF WEST PALM BEACH UTILITIES DEPARTMENT |
| AND THEIR CROSS CONNECTION PROGRAM ONLY ALLOW A REDUCED |
| ZONE PRESSURE VACUUM BREAKER. WOULD YOU PLEASE CORRECT |
| PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS? |
| |
| B. THE RZP WILL REQUIRE A SEPARATE PERMIT BY A LICENSED |
| CONTRACTOR AND CERTIFIED BY THE CITY OF WEST PALM BEACH |
| UTILITIES DEPARTMENT. WOULD YOU PLEASE ADD THIS ON THE |
| PAGE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS? |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |