2021-09-30 16:17:551ST REVIEW FBC-2020 RES.
 PERMIT- 21090524
 9/30/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-1: THE USE OF LEAD SHEET MATERIAL FOR THE
 SHOWER PAN LINER IS APPROVED ACCORDING TO SECTION
 P2709.2 FBC RES, ALTHOUGH THIS TYPE OF PAN LINER IS NOT
 TYPICALLY USED FOR RESIDENTIAL SHOWERS. THE DETAIL ON
 THE PLAN APPEARS TO BE COPIED AND PASTED. PLEASE VERIFY
 THIS THE TYPE OF LINER TO BE INSTALLED AS OPPOSED TO
 THE TYPICAL FACTORY-MADE PVC LINERS THAT ARE APPROVED
 UNDER P2709.2.1 FBC RES. A) PLEASE INDICATE THE SLOPE
 OF THE LINER IN THE DETAIL- SECTION P2709.3 FBC RES.
  
 2) PLEASE CORRECT THE 2-INCH WASHING MACHINE DRAIN
 STACK IN THE RISER TO SHOW A 3-INCH PER SECTION 406.2
 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  