2021-10-06 08:31:04 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT A ROOF DIAGRAM WITH DIMENSIONS, ROOF SLOPES | | AND MEAN ROOF HEIGHT SPECIFIED. SHOW GABLES AND HIPS. | | FBC AMENDMENTS 107.2.1 | | | | 2) SHOW THAT THE VALUE OF THE STRUCTURE IS LESS THAN | | $300,000.00 OR SPECIFY HOW THE ROOF TO WALL CONNECTIONS | | WILL BE IMPROVED. FBC EXISTING BUILDING 706.8 | | | | 3) THE POLYSTICK TU MAX THAT IS SPECIFIED IN THE | | PRODUCT APPROVAL FOR THE UNDERLAYMENTS IS NOT AN | | ALLOWABLE UNDERLAYMENT FOR ASPHALT SHINGLES PER TABLE 1 | | ON PAGE 5 OF THE PRODUCT APPROVAL. SELECT AN | | APPROPRIATE UNDERLAYMENT. FBC AMENDMENTS 107.2.1 |
|