2021-10-18 15:57:431ST REVIEW FBC-2020 RES.
 PERMIT- 21090968
 10/18/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER CORRECTIONS:
 A) THE NEW GENERATOR SPECS INDICATE 323.000 BTU LOAD,
 NOT 366,000- SECTION G2413.1 FBC RES.
 B) PROVIDE THE TOTAL BTU LOAD OF THE SYSTEM- G2413.2.
 C) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM-
 G2413.4.1.
 D) PROVIDE THE LENGTHS OF THE COPPER PIPING FROM THE
 REGULATOR TO THE GENERATOR AND POOL HEATER. PLEASE NOTE
 THAT BASED ON TABLE 402.4(10) FBC FG WHICH IS LISTED ON
 THE DRAWING, THE 1-INCH COPPER PIPE IS LIMITED TO 10
 FT. TOTAL RUN FOR THE 723,000 BTU LOAD.
 E) BASED ON TABLE 402.4(16) FBC FG, THE EHD 21 CSST IS
 UNDERSIZED FOR THE 282,000 BTU LOAD AT 48 FT. DEVELOPED
 LENGTH. PER THE TABLE MINIMUM EHD 30 IS REQUIRED TO THE
 1ST TEE, AND EHD 18 IS REQUIRED FROM THE TEE TO THE
 GRILL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  