2021-10-18 15:57:43 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21090968 |
| 10/18/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) GAS RISER CORRECTIONS: |
| A) THE NEW GENERATOR SPECS INDICATE 323.000 BTU LOAD, |
| NOT 366,000- SECTION G2413.1 FBC RES. |
| B) PROVIDE THE TOTAL BTU LOAD OF THE SYSTEM- G2413.2. |
| C) PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM- |
| G2413.4.1. |
| D) PROVIDE THE LENGTHS OF THE COPPER PIPING FROM THE |
| REGULATOR TO THE GENERATOR AND POOL HEATER. PLEASE NOTE |
| THAT BASED ON TABLE 402.4(10) FBC FG WHICH IS LISTED ON |
| THE DRAWING, THE 1-INCH COPPER PIPE IS LIMITED TO 10 |
| FT. TOTAL RUN FOR THE 723,000 BTU LOAD. |
| E) BASED ON TABLE 402.4(16) FBC FG, THE EHD 21 CSST IS |
| UNDERSIZED FOR THE 282,000 BTU LOAD AT 48 FT. DEVELOPED |
| LENGTH. PER THE TABLE MINIMUM EHD 30 IS REQUIRED TO THE |
| 1ST TEE, AND EHD 18 IS REQUIRED FROM THE TEE TO THE |
| GRILL. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |