Plan Review Notes
Plan Review Notes For Permit 21090962
Permit Number 21090962
Review Stop B
Sequence Number 3
Notes
Date Text
2021-11-04 13:58:21JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 PLEASE ADDRESS PREVIOUS COMMENTS BELOW DATED 10/27/2021
 AND RESUBMIT.
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON THE
 ROOF DRAWING. FBC AMEND. 107.2.1
 2) SPECIFY THE LOCATIONS AND HEIGHTS OF THE PARAPET
 WALLS ON THE ROOF DRAWING. FBC AMEND. 107.2.1
 3) SHOW THE LOCATIONS OF THE ROOF DRAINS AND/OR
 SCUPPERS ON THE ROOF DRAWING. FBC AMEND. 107.2.1
 4) PROVIDE A FLASHING DETAIL FOR THE PARAPET WALLS. FBC
 AMEND. 107.2.1
 5) THE ROOF REPORT INDICATES THAT THE PREDOMINATE PITCH
 IS 0:12. SECTION 706.1 OF THE FBC EXISTING BUILDING
 REQUIRES ROOFS TO HAVE POSITIVE DRAINAGE. SHOW
 COMPLIANCE ON THE ROOF PLAN.
 6) [THE SYSTEM THAT WAS MARKED ON PAGE 5 OF THE PRODUCT
 APPROVAL CANNOT BE USED. THE DESIGN PRESSURES OF -45
 PSF ARE TOO LOW AND CAN NOT BE INCREASED BY ENHANCED
 FASTENING PER LIMITATION #9.] THE PRODUCT APPROVALS FOR
 THE MULE-HIDE TPO ROOF SYSTEM HAS SEVERAL DIFFERENT
 ASSEMBLIES WITH DIFFERENT FASTENINGS AND DESIGN
 PRESSURES. PLEASE CIRCLE OR HI-LITE THE ONE THAT
 APPLIES TO THIS PROJECT. FBC AMEND. 107.2.1
 7) [SELECT THE FASTENING OPTION FOR THE APPROVED
 ASSEMBLY ON PAGE 6 AND SUBMIT SIGNED AND SEALED
 ENHANCED FASTENING CALCULATIONS AS SPECIFIED IN
 LIMITATION #7 ON PAGE 7 OF THE NOA.] THE MAXIMUM DESIGN
 PRESSURES ARE NOT ADEQUATE FOR THE PERIMETER AND CORNER
 AREAS. CHOOSE ONE THAT ALLOWS ENHANCED FASTENING AND
 SUBMIT SIGNED AND SEALED ENHANCED FASTENING
 CALCULATIONS FROM AN ENGINEER. ARCHITECT OR REGISTERED
 ROOFING CONSULTANT. SEE LIMITATION #7 ON PAGE 7 OF NOA
 NO.18-0109.09.
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
 9) SOME DOCUMENTS WERE SUBMITTED WITH THE ADDRESS OF
 3012 BROADWAY. THIS PERMIT IS FOR 3008 BROADWAY. SUBMIT
 ONLY DOCUMENTS THAT APPLY TO THIS PERMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  