2021-10-27 11:00:16 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON THE |
| ROOF DRAWING. FBC AMEND. 107.2.1 |
| 2) SPECIFY THE LOCATIONS AND HEIGHTS OF THE PARAPET |
| WALLS ON THE ROOF DRAWING. FBC AMEND. 107.2.1 |
| 3) SHOW THE LOCATIONS OF THE ROOF DRAINS AND/OR |
| SCUPPERS ON THE ROOF DRAWING. FBC AMEND. 107.2.1 |
| 4) PROVIDE A FLASHING DETAIL FOR THE PARPET WALLS. FBC |
| AMEND. 107.2.1 |
| 5) THE ROOF REPORT INDICATES THAT THE PREDOMINAT PITCH |
| IS 0:12. SECTION 706.1 OF THE FBC EXISTING BUILDING |
| REQUIRES ROOFS TO HAVE POSITIVE DRAINAGE. SHOW |
| COMPLIANCE ON THE ROOF PLAN. |
| 6) [THE SYSTEM THAT WAS MARKED ON PAGE 5 OF THE PRODUCT |
| APPROVAL CAN NOT BE USED. THE DESIGN PRESSURES OF -45 |
| PSF ARE TOO LOW AND CAN NOT BE INCREASED BY ENHANCED |
| FASTENING PER LIMITATION #9.] THE PRODUCT APPROVALS FOR |
| THE MULE-HIDE TPO ROOF SYSTEM HAS SEVERAL DIFFERENT |
| ASSEMBLIES WITH DIFFERENT FASTENINGS AND DESIGN |
| PRESSURES. PLEASE CIRCLE OR HI-LITE THE ONE THAT |
| APPLIES TO THIS PROJECT. FBC AMEND. 107.2.1 |
| 7) [SELECT THE FASTENING OPTION FOR THE APPROVED |
| ASSEMBLY ON PAGE 6 AND SUBMIT SIGNED AND SEALED |
| ENHANCED FASTENING CALCULATIONS AS SPECIFIED IN |
| LIMITATION #7 ON PAGE 7 OF THE NOA.] THE MAXIMUM DESIGN |
| PRESSURES ARE NOT ADEQUATE FOR THE PERIMETER AND CORNER |
| AREAS. CHOOSE ONE THAT ALLOWS ENHANCED FASTENING AND |
| SUBMIT SIGNED AND SEALED ENHANCED FASTENING |
| CALCULATIONS FROM AN ENGINEER. ARCHITECT OR REGISTERED |
| ROOFING CONSULTANT. SEE LIMITATION #7 ON PAGE 7 OF NOA |
| NO.18-0109.09. |
| 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. |
| 9) SOME DOCUMENTS WERE SUBMITTED WITH THE ADDRESS OF |
| 3012 BROADWAY. THIS PERMIT IS FOR 3008 BROADWAY. SUBMIT |
| ONLY DOCUMENTS THAT APPLY TO THIS PERMIT. |