Plan Review Notes
Plan Review Notes For Permit 21090948
Permit Number 21090948
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-12 08:57:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090948 505 S FLAGLER DR
  
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 GREASE INTERCEPTOR PER WPB FBC 105.1 & 107.2.1.
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOMS INDICATING THE FOLLOWING:
 ...A)CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1. TO BE CLEAR, THIS NEEDS TO BE
 NOTED ON THE PLAN.
 ...B)THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2. TO BE
 CLEAR, THIS NEEDS TO BE NOTED ON THE PLAN.
 ...C)FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ...D)THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
 ...E)MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890
 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 603.3.
  
 2. ALS1.1 PLUMBING FIXTURE CALCULATIONS SHALL BE BASED
 ON 2020 FLORIDA PLUMBING CODE, 7TH EDITION. PER WPB FBC
 107.2.1, PLEASE CORRECT.
  
 3. PER WPB FBC 107.2.1, PROVIDE A SLAB REPAIR DETAIL ON
 THE PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 4. TOILET RM 104 AND 106. P3-1; SHUT OFF VALVES ARE
 ABOVE A HARD CEILING. PER FBC PL 606.3, PROVIDE CEILING
 ACCESS PANELS.
  
 5. PROVIDE DETAIL FOR DISHWASHER NOTED ON A3.03/DETAIL
 10 IN COFFEE ROOM 110. SEE FBC PL 409.4. THE WASTE
 CONNECTION OF A RESIDENTIAL DISHWASHER SHALL CONNECT
 DIRECTLY TO A WYE BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK, DIRECTLY TO THE DISHWASHER CONNECTION
 OF A FOOD WASTE DISPOSER, OR THROUGH AN AIR BREAK TO A
 STANDPIPE. THE WASTE LINE OF A RESIDENTIAL DISHWASHER
 SHALL RISE AND BE SECURELY FASTENED TO THE UNDERSIDE OF
 THE SINK RIM OR COUNTER TOP.
  
 6. PER FBC PL 604.9, A WATER HAMMER ARRESTOR IS
 REQUIRED AT THE DISHWASHER.
  
 7. IN-LINE CHECK VALVES AT WATER CONNECTIONS TO COFFEE
 MAKER, ICE MAKERS ARE NOT BACKFLOW PREVENTERS. PER WPB
 FBC 107.2.1, SPECIFY LEAD FREE BACKFLOW PREVENTERS
 COMPLYING WITH FBC PL 608.1. DUAL CHECK VALVE/ ASSE
 1024 ARE ACCEPTABLE.
  
 8. P0.1 DETAIL FOR TEMPERED AND COLD WATER SUPPLY TO
 PUBLIC LAVATORIES LEONARD 170-LF-BRKT IS A POINT OF USE
 VALVE AND SHALL ONLY SUPPLY ONE LAVATORY. PER WPB FBC
 107.2.1, DELETE NOTE STATING IT CAN SUPPLY UP TO FIVE
 PUBLIC LAVATORIES.
  
 9. P0.1 DETAIL FOR ABOVE CEILING INSTANTANEOUS WATER
 HEATER IS NOT REFLECTED ON THE PLUMBING RISER DIAGRAM
 ON P5.1. PER WPB FBC 107.2.1, CLARIFY AND RECONCILE.
  
 10. PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING
 FIXTURE SCHEDULE THE MANUFACTURER OF THE GWH MODEL
 LT0540H-N. PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE SAME.
  
 11. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SUPPORT OF
 WALL MOUNTED WATER HEATER.
  
 12. RE: P5.1 SANITARY RISER DIAGRAM. FLOOR SINKS AND
 TRENCH DRAIN FIXTURE DRAINS SHALL BE PROVIDED WITH A
 WATER SEAL TRAP PER FBC PL 1002.1 PER WPB FBC 107.2.1,
 PROVIDE TRAPS ON THE SANITARY RISER DIAGRAM.. TRAPS
 SHALL ALL BE VENTED IN ACCORDANCE WITH FBC PL CHAPTER
 9.
  
 13. PER WPB FBC 107.2.1, INDICATE ON THE PLANS HOW THE
 TRAP SEAL FOR THE TRENCH DRAIN TRAPS ARE TO BE
 PROTECTED. SHOW COMPLIANCE WITH ONE OF THE METHODS
 DESCRIBED IN FBC PL 1002.4.1.1 THROUGH 1002.4.1.4.
  
 14. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 15. P3.1: ITEM 38, OVEN-STEAMER COMBINATION; PER WPB
 FBC 107.2.1, IDENTIFY ON PLAN. SPECIFY AND PROVIDE
 BACKFLOW PREVENTER PER FBC PL 608.1
  
 16. P3.1: ITEM 32; WAREWASHER. SPECIFY AND PROVIDE
 BACKFLOW PREVENTER PER FBC PL 608.1
  
 17. PER WPB FBC 107.2.1, RECIRC PUMP SCHEDULE & DETAIL;
 INCLUDE HP, ELECTRICAL CHARACTERISTICS, GPM, VALVES,
 ETC.
  
 18. PER WPB FBC 107.2.1, PROVIDE WATER SIZING
 CALCULATIONS. PROVIDE TABLE WITH FIXTURES AND EQUIPMENT
 SHOWING WSFU BREAKDOWN FOR COLD AND HOT WATER/GPM
 TOTALS
  
 19. PER WPB FBC 107.2.1, SANITARY PIPING SIZING
 CALCULATIONS. PROVIDE TABLE WITH FIXTURES/DRAINS AND
 SHOWING DFU BREAKDOWN AND TOTALS
  
 20. PER WPB FBC 107.2.1, GREASY WASTE PIPING SIZING
 CALCULATIONS. PROVIDE TABLE WITH FIXTURES/DRAINS AND
 SHOWING DFU BREAKDOWN AND TOTALS.
  
 21. PER WPB FBC 107.2.1, PROVIDE NOTE ON P5.1 ADJACENT
 TO SANITARY RISER DIAGRAM STATING FLOOR DRAINS, FLOOR
 SINKS AND TRENCH DRAINS ARE VENTED IN ACCORDANCE WITH
 FBC PL SECTION 915 COMBINATION WASTE AND VENT SYSTEM
  
 22. P2.1 APPEARS TO INDICATE A VERTICAL PIPE LOCATED
 BETWEEN THE TWO MOST UPSTREAM SINKS IN THE GREASY WASTE
 SYSTEM. P5.1 SANITARY RISER DIAGRAM DOES NOT SHOW THIS.
 PER WPB FBC 107.2.1, CLARIFY AND RECONCILE.
  
 23. PER WPB FBC 107.2.1, INDICATE AND SIZE THE MAIN
 VERTICAL VENT THAT PROVIDED IN ACCORDANCE WITH FBC PL
 915.2.3 AND 915.2.4. SAID VENT SHALL BE CONNECTED TO
 FULL SIZE BRANCH.
  
 24. P5.1, KEY NOTE 3 CALLS FOR NEW WATER METER AND
 BACKFLOW PREVENTER. P3.1, KEY NOTE 2 CALLS FOR
 CONNECTION TO EXISTING DOMESTIC WATER. PER WPB FBC
 107.2.1, CLARIFY AND RECONCILE.
  
 25. RE: COMMENT 24. PER WPB FBC 107.2.1, PROVIDE A
 DETAIL FOR THE APPLICABLE CONNECTION; INCLUDE ALL
 APPLICABLE METERS, BACKFLOW PREVENTERS AND VALVES.
  
 26. P3.1, KEY NOTE 2 CALLS FOR CONNECTION TO EXISTING
 DOMESTIC WATER. THERE IS A GAS CONNECTION POINT ON THE
 PLAN WHICH IS ALSO NOTED AS KEY NOTE 2. PER WPB FBC
 107.2.1, CLARIFY.
  
 27. P5.1, KEY NOTE 1 INDICATES EFFLUENT FROM GREASE
 INTERCEPTOR IS TO CONNECT TO EXISTING SEWER LATERAL;
 KEY NOTE 2 APPEARS TO SAY CONNECT NEW GREASY WASTE TO
 AN EXISTING INTERCEPTOR WITHOUT ACTUALLY STATING IT.
 PER WPB FBC 107.2.1, PLEASE CLARIFY. IS THIS A NEW
 INSTALLATION OR IS THE INTERCEPTOR EXISTING?
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090948 505 S FLAGLER DR
  
  
  
  