Notes
Date Text
2021-10-12 08:58:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090948 505 S FLAGLER DR
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1.TABLE 402.4(3) FOR 2 PSI SYSTEM IS INCORRECT.
 402.4(3) IS FOR LESS THAN 2 PSI/PD 3LBS/INITIAL SUPPLY
 PRESSURE 8 INCHES OR GREATER WATER COLUMN. SEE TABLE
 402.4(5) FOR 2 PSI/PD 1 LB.
  
 2.REGARDING 8-11 INCHES H20 SYSTEM, PLEASE CLARIFY WHAT
 IS MEANT BY H20. PLEASE NOTE, TABLE 402.4(2) IS FOR
 SYSTEMS LESS THAN 2 PSI/PD 0.5 INCHES WATER COLUMN.
  
 3.PROVIDE GAS EQUIPMENT SCHEDULE INDICATING BTU FOR
 EACH PIECE OF EQUIPMENT. LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE 2020 FBC FG SECS.401.8, 402.2, AND TABLES 402.4
 (1) THRU 402.4 (37)
  
 4.PER WPB FBC 107.2.1, INDICATE ON THE PLUMBING FIXTURE
 SCHEDULE THE MANUFACTURER OF THE GWH MODEL LT0540H-N.
 PROVIDE MANUFACTURER?S SPECIFICATION/INSTALLATION
 MANUAL FOR THE SAME.
  
 5.PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54
 AND FBC FG 402.2, AND 301.3. GAS APPLIANCES SHALL BE
 LISTED AND LABELED.
  
 6.THE INSTALLATION MANUALS FOR ALL GAS APPLIANCES /
 EQUIPMENT SHALL BE ONSITE AT THE TIME OF INSPECTION PER
 FBC FG 305.1.
  
 7.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE EMERGENCY
 HOOD SHOWING COMPLIANCE WITH NFPA 96-17; 10.4 AND 10.5.
 EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE SHALL BE BELOW
 THE CEILING. THE MANUAL SHUTOFF VALVE SHALL BE
 UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL VALVE. IN
 LIEU OF A DETAIL, A NOTE MAY BE PROVIDED ADJACENT TO
 THE GAS RISER DIAGRAM STATING PER NFPA 96-17, SECTIONS
 10.4 AND 10.5, EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE
 SHALL BE BELOW THE CEILING. THE MANUAL SHUT OFF VALVE
 SHALL BE UPSTREAM. UNION TO BE DOWN STREAM OF MANUAL
 VALVE.
  
 8.SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE
 REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE
 BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER
 FBC FG 410.1.
  
 9. P3.1, KEY NOTE 2 CALLS FOR CONNECTION TO EXISTING
 DOMESTIC WATER. THERE IS A GAS CONNECTION POINT ON THE
 PLAN WHICH IS ALSO NOTED AS KEY NOTE 2. PER WPB FBC
 107.2.1, CLARIFY.
  
 10.THE SAME SYMBOL IS SHOWN ON P3.1 AND P5.1 AT THE GAS
 METER LOCATION AND FOR THE EMERGENCY HOOD SHUT
 OFF/ANSUL VALVE. THE SYMBOL CHART ON P0.1 DOES NOT
 IDENTIFY THAT SYMBOL. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
  
 11.PER WPB FBC 107.2.1, SPECIFY THE MP REGULATORS.;
 PROVIDE AN INSTALLATION DETAIL FOR THE MP REGULATORS.
 SHOW COMPLIANCE WITH
 ?A)FBC FG 409.4, A LISTED SHUTOFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR
 ?B)AND 410.2 AS FOLLOWS:
 .....1)THE MP REGULATOR SHALL BE APPROVED AND SHALL BE
 SUITABLE FOR THE INLET AND OUTLET GAS PRESSURES FOR THE
 APPLICATION.
 .....2)THE MP REGULATOR SHALL MAINTAIN A REDUCED OUTLET
 PRESSURE UNDER LOCK-UP (NO-FLOW) CONDITIONS.
 .....3)THE CAPACITY OF THE MP REGULATOR, DETERMINED BY
 PUBLISHED RATINGS OF ITS MANUFACTURER, SHALL BE
 ADEQUATE TO SUPPLY THE APPLIANCES SERVED.
 .....4)THE MP PRESSURE REGULATOR SHALL BE PROVIDED WITH
 ACCESS. WHERE LOCATED INDOORS, THE REGULATOR SHALL BE
 VENTED TO THE OUTDOORS OR SHALL BE EQUIPPED WITH A
 LEAK-LIMITING DEVICE, IN EITHER CASE COMPLYING WITH
 SECTION 410.3.
 .....5)A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED BETWEEN THE MP REGULATOR AND ITS
 UPSTREAM SHUTOFF VALVE. SUCH TEE FITTING SHALL BE
 POSITIONED TO ALLOW CONNECTION OF A PRESSURE-MEASURING
 INSTRUMENT AND TO SERVE AS A SEDIMENT TRAP.
 .....6)A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED
 SHALL BE INSTALLED NOT LESS THAN 10 PIPE DIAMETERS
 DOWNSTREAM OF THE MP REGULATOR OUTLET. SUCH TEE FITTING
 SHALL BE POSITIONED TO ALLOW CONNECTION OF A
 PRESSURE-MEASURING INSTRUMENT. THE TEE FITTING IS NOT
 REQUIRED WHERE THE MP REGULATOR SERVES AN APPLIANCE
 THAT HAS A PRESSURE TEST PORT ON THE GAS CONTROL INLET
 SIDE AND THE APPLIANCE IS LOCATED IN THE SAME ROOM AS
 THE MP REGULATOR.
 .....7)WHERE CONNECTED TO RIGID PIPING, A UNION SHALL
 BE INSTALLED WITHIN 1 FOOT (304 MM) OF EITHER SIDE OF
 THE MP REGULATOR.
  
 12.PER WPB FBC 107.2.1, SPECIFY MANUAL GAS SHUT OFF
 VALVES. VALVES SHALL COMPLY WITH FBC FG 409.1.1/TABLE
 409.1.1, LISTED IN ACCORDANCE WITH FBC FG 409.4.
  
 13.PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR THE GAS
 METER/REGULATOR SHOWING VALVE(S) AND UNION(S)
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  