Plan Review Notes For Permit 21090948 |
Permit Number |
21090948 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-10-22 13:44:52 | GROUND FLOOR ALTERATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | 1) PLEASE SHOW WALL AND CEILING FINISHES FIRE | | CLASSIFICATION TO COMPLY WITH FBC TABLE 803.11 | | | | 2) BUILDING CONSTRUCTION TYPE SHOWN ON DRAWING ALS1.1 | | MAY BE INCORRECT - SHOWN IS CONSTRUCTION TYPE IIIB | | WHICH IS LIMITED IN STORIES - HOW MANY STORIES ARE IN | | THE BUILDING - PLEASE RE EVALUATE PER FBC CHAPTER 5 | | | | 3) PLEASE PROVIDE THE EXTERIOR LOADING RAMP | | CONSTRUCTION DETAILS. | | | | 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR HEIGHT | | FROM THE FINISHED FLOOR TO THE "REFLECTIVE SURFACE" - | | FBC A 603.3 MIRRORS. | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. |
|