2021-10-22 13:44:52GROUND FLOOR ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW WALL AND CEILING FINISHES FIRE
 CLASSIFICATION TO COMPLY WITH FBC TABLE 803.11
  
 2) BUILDING CONSTRUCTION TYPE SHOWN ON DRAWING ALS1.1
 MAY BE INCORRECT - SHOWN IS CONSTRUCTION TYPE IIIB
 WHICH IS LIMITED IN STORIES - HOW MANY STORIES ARE IN
 THE BUILDING - PLEASE RE EVALUATE PER FBC CHAPTER 5
  
 3) PLEASE PROVIDE THE EXTERIOR LOADING RAMP
 CONSTRUCTION DETAILS.
  
 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR HEIGHT
 FROM THE FINISHED FLOOR TO THE "REFLECTIVE SURFACE" -
 FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.