Plan Review Notes For Permit 21090724 |
Permit Number |
21090724 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-09-30 17:15:29 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | 1) THE MAXIMUM DESIGN PRESSURE FOR THE TARKO | | SELF-ADHERING MODIFIED ROOFING SYSTEM ON PAGE 10 OF THE | | NOA HAS A MAXIMUM DESIGN PRESSURE OF 60 PSF WHICH IS | | NOT ADEQUATE FOR THE PERIMETER AND CORNER ROOF AREAS. | | SUBMIT SIGNED AND SEALED ENHANCED FASTENING | | CALCULATIONS IN ACCORDANCE WITH LIMITATION NUMBER 7 OF | | THE PRODUCT APPROVAL. FBC-R301 | | 2) THE UNDERLAYMENT FOR THE ASPHALT SHINGLES IS | | REQUIRED TO COMPLY WITH FBC-R905.1.1.1. SPECIFY WHICH | | METHOD WILL BE USED AND SUBMIT THE PRODUCT APPROVAL FOR | | IT. |
|