2021-10-06 11:33:05 | 10/06/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW, |
| AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SECOND REQUEST, A WASHING MACHINE HOOK-UP FOR THIS |
| UNIT AS REQUIRED IN THE 2020 FBC SEC. P TABLE 403.1 |
| |
| 3. ON SHEET A-5B FOR THE SECOND FLOOR SHOWS A TANK-LESS |
| WATER HEATER, AND THE LOCATION IS ON THE SECOND FLOOR |
| IS NOT ACCESSIBLE FOR SERVICE PER MANUFACTURERS |
| SPECIFICATION. WOULD YOU PLEASE PROVIDE A DIFFERENT |
| LOCATION AND GIVE THE DISTANCE OF ANY OPERABLE DOORS OR |
| WINDOWS IN RELATION TO THE WATER HEATER? THE SITE OF |
| THE WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE |
| INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| 403.5.3. WOULD YOU PLEASE PLACE A NOTE ON PLANS? |
| |
| 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. WOULD YOU PLEASE PLACE A NOTE ON |
| PLANS? |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, DESCRIBING THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |
| |