Plan Review Notes
Plan Review Notes For Permit 21090720
Permit Number 21090720
Review Stop P
Sequence Number 2
Notes
Date Text
2021-10-06 11:33:0510/06/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW,
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SECOND REQUEST, A WASHING MACHINE HOOK-UP FOR THIS
 UNIT AS REQUIRED IN THE 2020 FBC SEC. P TABLE 403.1
  
 3. ON SHEET A-5B FOR THE SECOND FLOOR SHOWS A TANK-LESS
 WATER HEATER, AND THE LOCATION IS ON THE SECOND FLOOR
 IS NOT ACCESSIBLE FOR SERVICE PER MANUFACTURERS
 SPECIFICATION. WOULD YOU PLEASE PROVIDE A DIFFERENT
 LOCATION AND GIVE THE DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER? THE SITE OF
 THE WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. WOULD YOU PLEASE PLACE A NOTE ON PLANS?
  
 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1. WOULD YOU PLEASE PLACE A NOTE ON
 PLANS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  
  