2021-10-20 07:27:29 | ROOFING PLAN REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 2ND REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. SYSTEM W-84 HAS BEEN SELECTED FROM PRODUCT APPROVAL |
| FL2533-R25. THE DESIGN PRESSURE OF -105.0 DOES NOT MEET |
| OR EXCEED THE DESIGN PRESSURE OF THE ROOF PER FBC R |
| CHPT 3. |
| PER TABLE R301.2 (2), THE DESIGN PRESSURE OF THE ROOF |
| IS -89.4. A COEFFICIENT OF 1.21 MUST BE APPLIED BASED |
| ON VULT OF 170MPH AND EXPOSURE C PER TABLE R301.2 (3). |
| THIS CALCULATION DETERMINES THE DESIGN PRESSUTRE OF THE |
| ROOF TO BE -108.2. |
| EITHER PROVIDE ENHANCED FASTENER CALCULATIONS, PER |
| LIMITATIONS NOTE 5.6.1, OF THE PRODUCT APPROVAL OR |
| CHOOSE ANOTHER SYSTEM THAT MEETS OR EXCEEDS THE DESIGN |
| PRESSURE OF THE ROOF (-108.3). |
| |
| 2. WHEN SUBMITTING DOCUMENTS FOR REVIEW, UPLOAD THE |
| COMPLETE NOA OR PRODUCT APPROVAL FOR REVIEW. WE CANNOT |
| REPLACE A SINGLE PAGE OF AN NOA OR PRODUCT APPROVAL. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| |