2021-10-20 07:27:29ROOFING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SYSTEM W-84 HAS BEEN SELECTED FROM PRODUCT APPROVAL
 FL2533-R25. THE DESIGN PRESSURE OF -105.0 DOES NOT MEET
 OR EXCEED THE DESIGN PRESSURE OF THE ROOF PER FBC R
 CHPT 3.
 PER TABLE R301.2 (2), THE DESIGN PRESSURE OF THE ROOF
 IS -89.4. A COEFFICIENT OF 1.21 MUST BE APPLIED BASED
 ON VULT OF 170MPH AND EXPOSURE C PER TABLE R301.2 (3).
 THIS CALCULATION DETERMINES THE DESIGN PRESSUTRE OF THE
 ROOF TO BE -108.2.
 EITHER PROVIDE ENHANCED FASTENER CALCULATIONS, PER
 LIMITATIONS NOTE 5.6.1, OF THE PRODUCT APPROVAL OR
 CHOOSE ANOTHER SYSTEM THAT MEETS OR EXCEEDS THE DESIGN
 PRESSURE OF THE ROOF (-108.3).
  
 2. WHEN SUBMITTING DOCUMENTS FOR REVIEW, UPLOAD THE
 COMPLETE NOA OR PRODUCT APPROVAL FOR REVIEW. WE CANNOT
 REPLACE A SINGLE PAGE OF AN NOA OR PRODUCT APPROVAL.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  