2021-09-30 17:38:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE W-79 ROOFING SYSTEM THAT YOU SELECTED ON PAGE 15
 OF THE CERTAINTEED PRODUCT APPROVAL HAS A MAXIMUM
 DESIGN PRESSURE OF -60 PSF. THIS IS NOT ADEQUATE FOR
 THE PERIMETER AND CORNER AREAS FOR THIS PROJECT. THE
 WIND SPEED IS 170 MPH VULT AND THE EXPOSURE CATEGORY IS
 C. SUBMIT SIGNED AND SEALED ENHANCED FASTENING
 CALCULATIONS IF ALLOWED BY THE PRODUCT APPROVAL OR
 SELECT ANOTHER SYSTEM. FBC-R301