Plan Review Notes For Permit 21090716 |
Permit Number |
21090716 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-09-30 17:38:13 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE W-79 ROOFING SYSTEM THAT YOU SELECTED ON PAGE 15 | | OF THE CERTAINTEED PRODUCT APPROVAL HAS A MAXIMUM | | DESIGN PRESSURE OF -60 PSF. THIS IS NOT ADEQUATE FOR | | THE PERIMETER AND CORNER AREAS FOR THIS PROJECT. THE | | WIND SPEED IS 170 MPH VULT AND THE EXPOSURE CATEGORY IS | | C. SUBMIT SIGNED AND SEALED ENHANCED FASTENING | | CALCULATIONS IF ALLOWED BY THE PRODUCT APPROVAL OR | | SELECT ANOTHER SYSTEM. FBC-R301 |
|