Plan Review Notes
Plan Review Notes For Permit 21090703
Permit Number 21090703
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-06 12:54:451ST REVIEW FBC-2020 RES.
 PERMIT- 21090703
 10/6/2021
  
 CODES IN EFFECT:
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P100: PROVIDE A SANITARY DRAINAGE AND VENT
 ISOMETRIC DRAWING- SECTION 107.3.5.3 WPB.
  
 2) P100: PLEASE PROVIDE A PLUMBING SCOPE OF WORK
 NARRATIVE ON THE PLAN. INDICATE WHICH FIXTURES,
 APPLIANCES, FAUCETS ETC. ARE BEING REPLACED- SECTION
 107.2.1 WPB.
  
 3) P100: PROVIDE THE MAKE AND MODEL OF THE NEW WATER
 HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- TABLE
 C404.2 FBC EC AND SECTION P2801.1 FBC RES.
  
 4) P100: PROVIDE HOT WATER PIPE SPECIFICATIONS- TABLE
 C403.2.10 FBC EC.
  
 5) P100: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR
 THE STEAM EQUIPMENT AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 107.2.1 WPB. PROVIDE A PIPING
 DIAGRAM ON THE PLAN- SECTION 107.3.5.3 WPB.
  
 6) FLOOD ZONE HAZARD: THE PROPERTY APPEARS TO BE IN AN
 AE FLOOD HAZARD ZONE. ACCORDING TO SECTION R322.1.6 FBC
 RES, PLUMBING FIXTURES, APPLIANCES, PIPING ETC. SHALL
 BE INSTALLED AT OR ABOVE THE ELEVATION REQUIRED IN
 SECTION R322.2 FBC RES.
  
 7) PLEASE SHOW COMPLIANCE WITH R322.1.7 PROTECTION OF
 WATER SUPPLY AND SANITARY SEWAGE SYSTEMS NEW WATER
 SUPPLY AND SANITARY PIPING SYSTEMS. NEW AND REPLACEMENT
 WATER SUPPLY SYSTEMS SHALL BE DESIGNED TO MINIMIZE OR
 ELIMINATE INFILTRATION OF FLOOD WATERS INTO THE SYSTEMS
 IN ACCORDANCE WITH THE PLUMBING PROVISIONS OF THIS
 CODE. NEW AND REPLACEMENT SANITARY SEWAGE SYSTEMS SHALL
 BE DESIGNED TO MINIMIZE OR ELIMINATE INFILTRATION OF
 FLOODWATERS INTO SYSTEMS AND DISCHARGES FROM SYSTEMS
 INTO FLOODWATERS IN ACCORDANCE WITH THE PLUMBING
 PROVISIONS OF THIS CODE AND IN ACCORDANCE WITH CHAPTER
 64E-6, FLORIDA ADMINISTRATIVE CODE, STANDARDS FOR
 ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEMS. SEE ALSO
 SECTION 7.3 ASCE 24-14.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  