2021-10-06 12:54:45 | 1ST REVIEW FBC-2020 RES. |
| PERMIT- 21090703 |
| 10/6/2021 |
| |
| CODES IN EFFECT: |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P100: PROVIDE A SANITARY DRAINAGE AND VENT |
| ISOMETRIC DRAWING- SECTION 107.3.5.3 WPB. |
| |
| 2) P100: PLEASE PROVIDE A PLUMBING SCOPE OF WORK |
| NARRATIVE ON THE PLAN. INDICATE WHICH FIXTURES, |
| APPLIANCES, FAUCETS ETC. ARE BEING REPLACED- SECTION |
| 107.2.1 WPB. |
| |
| 3) P100: PROVIDE THE MAKE AND MODEL OF THE NEW WATER |
| HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- TABLE |
| C404.2 FBC EC AND SECTION P2801.1 FBC RES. |
| |
| 4) P100: PROVIDE HOT WATER PIPE SPECIFICATIONS- TABLE |
| C403.2.10 FBC EC. |
| |
| 5) P100: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR |
| THE STEAM EQUIPMENT AND SUBMIT MANUFACTURER'S |
| SPECIFICATIONS- SECTION 107.2.1 WPB. PROVIDE A PIPING |
| DIAGRAM ON THE PLAN- SECTION 107.3.5.3 WPB. |
| |
| 6) FLOOD ZONE HAZARD: THE PROPERTY APPEARS TO BE IN AN |
| AE FLOOD HAZARD ZONE. ACCORDING TO SECTION R322.1.6 FBC |
| RES, PLUMBING FIXTURES, APPLIANCES, PIPING ETC. SHALL |
| BE INSTALLED AT OR ABOVE THE ELEVATION REQUIRED IN |
| SECTION R322.2 FBC RES. |
| |
| 7) PLEASE SHOW COMPLIANCE WITH R322.1.7 PROTECTION OF |
| WATER SUPPLY AND SANITARY SEWAGE SYSTEMS NEW WATER |
| SUPPLY AND SANITARY PIPING SYSTEMS. NEW AND REPLACEMENT |
| WATER SUPPLY SYSTEMS SHALL BE DESIGNED TO MINIMIZE OR |
| ELIMINATE INFILTRATION OF FLOOD WATERS INTO THE SYSTEMS |
| IN ACCORDANCE WITH THE PLUMBING PROVISIONS OF THIS |
| CODE. NEW AND REPLACEMENT SANITARY SEWAGE SYSTEMS SHALL |
| BE DESIGNED TO MINIMIZE OR ELIMINATE INFILTRATION OF |
| FLOODWATERS INTO SYSTEMS AND DISCHARGES FROM SYSTEMS |
| INTO FLOODWATERS IN ACCORDANCE WITH THE PLUMBING |
| PROVISIONS OF THIS CODE AND IN ACCORDANCE WITH CHAPTER |
| 64E-6, FLORIDA ADMINISTRATIVE CODE, STANDARDS FOR |
| ONSITE SEWAGE TREATMENT AND DISPOSAL SYSTEMS. SEE ALSO |
| SECTION 7.3 ASCE 24-14. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |