2021-10-06 13:54:57 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 21090703 |
| 10/6/2021 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P100: PROVIDE A COMPLETE GAS RISER DRAWING |
| THAT INCLUDES ALL NEW AND EXISTING GAS PIPING AND |
| APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & G2412.4 |
| FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- THE |
| RISER SHALL INDICATE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) P100: PROVIDE THE MAKE AND MODEL OF THE NEW WATER |
| HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- TABLE |
| C404.2 FBC EC AND SECTION G2448.1 FBC RES. INDICATE HOW |
| COMBUSTION WILL BE SUPPLIED TO THE WATER HEATER AND |
| PROVIDE A GAS VENTING PLAN- SECTIONS G2407.1,G2427.1 & |
| G2448.1 FBC RES. |
| |
| 3) P100: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW |
| RANGE AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION |
| G2447.1 FBC RES. PROVIDE COMBUSTION AIR CALCULATIONS |
| AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION |
| G2407.1 FBC RES. |
| |
| 4) P100: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW |
| FIREPLACE AND SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION MANUAL - SECTION G2434.1 FBC RES. PROVIDE |
| COMBUSTION AIR AND VENTING PLANS FOR THE FIREPLACE IN |
| ACCORDANCE WITH MANUFACTURER'S GUIDELINES. PLEASE |
| INCLUDE COMBUSTION AIR CALCULATIONS, AND A VENTING |
| DIAGRAM WHICH SHOWS THE TYPE AND SIZE OF VENT |
| PIPES/DUCTS, VENT RUN LENGTHS AND VENT TERMINATION |
| LOCATION- REFER TO SPECS AND SECTION G2427 FBC RES. |
| |
| 5) P100: PROVIDE AN EQUIPMENT SCHEDULE FOR THE GAS |
| GRILL AND SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION MANUAL- G2408.1 & G2447.1 FBC RES. |
| |
| 6) P100: PROVIDE AN ELEVATION VIEW DRAWING OF THE |
| BUILT-IN GAS GRILL SHOWING CLEARANCES TO COMBUSTIBLES |
| AND OVERHEAD CONSTRUCTION PER THE MANUFACTURER?S |
| RECOMMENDATIONS. PLEASE NOTE THAT MANY OF THE GRILL |
| MANUFACTURER'S DO NOT ALLOW INSTALLATIONS IN ENCLOSED |
| OR PARTIALLY ENCLOSED STRUCTURES WITH OVERHEAD |
| CONSTRUCTION UNLESS A HOOD AND EXHAUST VENT SYSTEM IS |
| INSTALLED- G2408.1 & G2447.1 FBC RES. |
| |
| 7) P100: INDICATE THE MAKES AND MODELS OF REGULATORS TO |
| BE INSTALLED ON THE SYSTEM AND SUBMIT MANUFACTURER?S |
| SPECIFICATIONS MARKED UP TO SHOW THE SELECTED MODELS, |
| AND INPUT AND OUT PIPE SIZES AND PRESSURES- SECTION |
| G2421.2 FBC RES. |
| |
| 8) FLOOD ZONE HAZARD: THE PROPERTY APPEARS TO BE IN AN |
| AE FLOOD HAZARD ZONE. ACCORDING TO SECTION R322.1.6 FBC |
| RES THE GAS PIPING AND GAS-FIRED APPLIANCES AND |
| EQUIPEMENT SHALL BE INSTALLED AT OR ABOVE THE ELEVATION |
| REQUIRED IN SECTION R322.2 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |