2021-10-06 13:54:571ST REVIEW FBC-2020 RES. GAS
 PERMIT- 21090703
 10/6/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P100: PROVIDE A COMPLETE GAS RISER DRAWING
 THAT INCLUDES ALL NEW AND EXISTING GAS PIPING AND
 APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & G2412.4
 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- THE
 RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) P100: PROVIDE THE MAKE AND MODEL OF THE NEW WATER
 HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- TABLE
 C404.2 FBC EC AND SECTION G2448.1 FBC RES. INDICATE HOW
 COMBUSTION WILL BE SUPPLIED TO THE WATER HEATER AND
 PROVIDE A GAS VENTING PLAN- SECTIONS G2407.1,G2427.1 &
 G2448.1 FBC RES.
  
 3) P100: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW
 RANGE AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 G2447.1 FBC RES. PROVIDE COMBUSTION AIR CALCULATIONS
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION
 G2407.1 FBC RES.
  
 4) P100: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW
 FIREPLACE AND SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL - SECTION G2434.1 FBC RES. PROVIDE
 COMBUSTION AIR AND VENTING PLANS FOR THE FIREPLACE IN
 ACCORDANCE WITH MANUFACTURER'S GUIDELINES. PLEASE
 INCLUDE COMBUSTION AIR CALCULATIONS, AND A VENTING
 DIAGRAM WHICH SHOWS THE TYPE AND SIZE OF VENT
 PIPES/DUCTS, VENT RUN LENGTHS AND VENT TERMINATION
 LOCATION- REFER TO SPECS AND SECTION G2427 FBC RES.
  
 5) P100: PROVIDE AN EQUIPMENT SCHEDULE FOR THE GAS
 GRILL AND SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL- G2408.1 & G2447.1 FBC RES.
  
 6) P100: PROVIDE AN ELEVATION VIEW DRAWING OF THE
 BUILT-IN GAS GRILL SHOWING CLEARANCES TO COMBUSTIBLES
 AND OVERHEAD CONSTRUCTION PER THE MANUFACTURER?S
 RECOMMENDATIONS. PLEASE NOTE THAT MANY OF THE GRILL
 MANUFACTURER'S DO NOT ALLOW INSTALLATIONS IN ENCLOSED
 OR PARTIALLY ENCLOSED STRUCTURES WITH OVERHEAD
 CONSTRUCTION UNLESS A HOOD AND EXHAUST VENT SYSTEM IS
 INSTALLED- G2408.1 & G2447.1 FBC RES.
  
 7) P100: INDICATE THE MAKES AND MODELS OF REGULATORS TO
 BE INSTALLED ON THE SYSTEM AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS MARKED UP TO SHOW THE SELECTED MODELS,
 AND INPUT AND OUT PIPE SIZES AND PRESSURES- SECTION
 G2421.2 FBC RES.
  
 8) FLOOD ZONE HAZARD: THE PROPERTY APPEARS TO BE IN AN
 AE FLOOD HAZARD ZONE. ACCORDING TO SECTION R322.1.6 FBC
 RES THE GAS PIPING AND GAS-FIRED APPLIANCES AND
 EQUIPEMENT SHALL BE INSTALLED AT OR ABOVE THE ELEVATION
 REQUIRED IN SECTION R322.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  