2021-11-01 14:28:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE EDGE DISTANCE WAS CHANGED TO 3 1/2", SO THE
 FACTOR IS NO LONGER REQUIRED BUT THE INSTALLATION
 SCHEDULE STILL STATES THAT THERE IS A .9 FACTOR. PLEASE
 REMOVE THIS LANGUAGE OR CLARIFY WHY THE LANGUAGE IS
 THERE.
  
 2. OPENINGS 6 AND 7 HAVE DESIGN PRESSURES OVER 40PSF,
 BUT 40PSF ANCHOR SPACING IS PROPOSED, SEE PAGE 12.