Plan Review Notes For Permit 21090695 |
Permit Number |
21090695 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-11-01 14:28:04 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. THE EDGE DISTANCE WAS CHANGED TO 3 1/2", SO THE | | FACTOR IS NO LONGER REQUIRED BUT THE INSTALLATION | | SCHEDULE STILL STATES THAT THERE IS A .9 FACTOR. PLEASE | | REMOVE THIS LANGUAGE OR CLARIFY WHY THE LANGUAGE IS | | THERE. | | | | 2. OPENINGS 6 AND 7 HAVE DESIGN PRESSURES OVER 40PSF, | | BUT 40PSF ANCHOR SPACING IS PROPOSED, SEE PAGE 12. |
|