2022-05-16 17:58:58 | BUILDING REVIEW APPROVED WITH PROVISO: | | (NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO | | INSTALLATION/INSPECTION TO AVOID CONFLICTS/DELAYS). | | 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE | | CONSTRUCTION OF HANDRAILS AND GUARDRAILS SHOWING | | COMPLIANCE WITH TABLE R301.5, SEC. R311.7.8 AND SEC. | | R312.1 FBC-RESIDENTIAL. | | | | 2- PROVIDE PRODUCT APPROVAL FOR: | | A)HARDIE PLANK SIDING. B)ALL EXTERIOR DOORS. C)WINDOW | | MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE TO AVOID | | DELAYS/CONFLICTS). D)COLONIAL SHUTTERS A SHOWN ON PLANS | | AND PROVIDE INSTALLATION SCHEDULE. E)ROOFING | | UNDERLAYMENT SPECIFIED ON ONE & TWO STORY WALL | | SECTIONS. F)GABLE VENTS SHOWN ON PLANS. G)METAL | | ROOFING. H)HORIZONTAL ROLLER WINDOWS. I)ENTRY DOORS. | | J)OVERHEAD GARAGE DOOR. | | | | 3- ARCHITECT TO REVIEW/APPROVE ALL PRODUCT APPROVALS. | | | | 4- REVISE THE ENERGY CALCULATIONS: | | A)CLARIFY IF CALCULATIONS ARE FOR ENTIRE HOUSE OR JUST | | THE ADDITION. REVISE ACCORDINGLY. B)REVISE ITEM #9(A). | | THERE IS NO RAISED FLOOR IN THIS HOUSE. C)REVISE THE | | ATTIC VENT RATIO. D)DOORS INFORMATION IS INCORRECT. | | E)REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS. |
|