2022-03-17 10:06:381ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090688
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS ARE FOR A 2 STORY ADDITION FOR AN
 EXISTING HOUSE FOR A TOTAL OF 2992 SQUARE FOOT OF NEW
 SPACE. IN THE MECHANICAL EQUIPMENT SIZING CALCULATIONS,
 ZONE 1 IS FOR THE 1ST FLOOR ADDITION SQUARE FOOTAGE
 WHICH IS 1496. THE AHU 1 IS LOCATED IN THE GARAGE AND
 HAS DUCTWORK THROUGHOUT THE ENTIRE FIRST FLOOR WHICH
 INCLUDES THE EXISTING SQUARE FOOTAGE OF THE HOME. IF
 AHU-1 IS TO CONDITION BOTH THE EXISTING SQUARE FOOTAGE
 AND THE NEW SQUARE FOOTAGE OF THE 1ST FLOOR YOU MUST
 PROVIDE A MECHANICAL EQUIPMENT SIZING CALCULATION FOR
 THE ENTIRE 1ST FLOOR AREA AND SIZE AHU-1 ACCORDINGLY.
 IT DOES NOT APPEAR THAT AHU-1 COULD BE SIZED THE SAME
 AS AHU-2 AS AHU-1 SERVES A LARGER SQUARE FOOTAGE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER