2022-03-17 10:06:38 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21090688 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT |
| SIZING CALCULATIONS ARE FOR A 2 STORY ADDITION FOR AN |
| EXISTING HOUSE FOR A TOTAL OF 2992 SQUARE FOOT OF NEW |
| SPACE. IN THE MECHANICAL EQUIPMENT SIZING CALCULATIONS, |
| ZONE 1 IS FOR THE 1ST FLOOR ADDITION SQUARE FOOTAGE |
| WHICH IS 1496. THE AHU 1 IS LOCATED IN THE GARAGE AND |
| HAS DUCTWORK THROUGHOUT THE ENTIRE FIRST FLOOR WHICH |
| INCLUDES THE EXISTING SQUARE FOOTAGE OF THE HOME. IF |
| AHU-1 IS TO CONDITION BOTH THE EXISTING SQUARE FOOTAGE |
| AND THE NEW SQUARE FOOTAGE OF THE 1ST FLOOR YOU MUST |
| PROVIDE A MECHANICAL EQUIPMENT SIZING CALCULATION FOR |
| THE ENTIRE 1ST FLOOR AREA AND SIZE AHU-1 ACCORDINGLY. |
| IT DOES NOT APPEAR THAT AHU-1 COULD BE SIZED THE SAME |
| AS AHU-2 AS AHU-1 SERVES A LARGER SQUARE FOOTAGE. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |