2022-03-16 13:46:01RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21090688.
  
 ******IMPORTANT*****
 THERE WAS A MISTAKE WHEN UPLOADING DRAWINGS TO
 PROJECTDOX. DRAWING S-2 WAS UPLOADED AND VERSIONED WITH
 FOUNDATION DRAWING S-1. NEED TO UPLOAD DRAWING DRAWING
 S-1 AGAIN AND VERSIONED WITH CORRECT FILE.
  
  
 NOTE:
 NEED RETAINING WALL PERMIT AT TIME OF BUILDING PERMIT
 TO AVOID CONFLICTS/DELAYS.
  
  
 ORIGINAL COMMENT:
 1- LOT DRAINAGE
 PROVIDE COMPLETE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 THE FOLLOWING: SEC. R401.3 FBC-RESIDENTIAL. SEC.
 107.2.5 CITY AMENDMENTS. SEC. 110.9 CITY AMENDMENTS.
 NOTE: PROPOSED ADDITIONS ARE TO CLOSE TO THE NEIGHBOR
 ON THE EAST SIDE. DRAINAGE PLAN TO SHOW THE EXISTING
 AND PROPOSED GRADE ELEVATIONS SHOWING HOW KEEPING WATER
 AWAY FROM ADJACENT PROPERTIES.
  
 RESPONSE:
 DRAINAGE PLAN ON SHEET DR-1 NOW SHOWS THE PROPOSED
 ADDITION WITH A FINISHED FLOOR ELEVATION OF 12.44" FOR
 THE 2 STORY ADDITION AND 12' FOR THE GARAGE ADDITION.
 DRAINAGE PLAN DOESN'T SHOW THE PROPOSED GRADE
 ELEVATIONS ON THE EAST SIDE OF THESE TWO ADDITIONS.
 DRAINAGE PLAN ONLY SHOWS AN EXISTING 10.84 GRADE
 ELEVATION WHERE THE PROPOSED 2 STORY ADDITION IS GOING
 TO BE BUILT. THERE IS A CONCERN FOR DRAINAGE IN THE
 NARROW AREA BETWEEN THE NEW BUILDINGS AND THE 5'-1"
 SETBACK BECAUSE OF THE ADDITION PROPOSED FINISHED FLOOR
 ELEVATION.
 DRAINAGE PLAN SPECIFIES A RETAINING WALL ON THE EAST
 SIDE UNDER A SEPARATE PERMIT. NOTE: CLEARLY INDICATE ON
 PLAN THE EXTEND OF RETAINING WALL AND PROVIDE
 STRUCTURAL DETAIL OF WALL. HOW IS THE STACKED BLOCK
 REINFORCED TO STAY IN PLACE. SEC. R301.1
 FBC-RESIDENTIAL. ALSO, PROVIDE SECTION/DETAIL AND
 SPECIFICATIONS WITH GRADE ELEVATIONS SHOWING HOW
 DIVERTING SURFACE WATER AWAY FROM THE FOUNDATION (SEC.
 R401.3 FBC-RESIDENTIAL).
 NOTE: SINCE THE PROPOSED RETAINING WALL AFFECTS THE
 FOUNDATION WORK, THEN THE RETAINING WALL PERMIT NEEDS
 TO BE COORDINATED WITH THIS PERMIT TO AVOID
 CONFLICTS/DELAYS.
  
 2-OK.
 3-OK.
 4-OK.
  
 5-DEFERRED SUBMITTAL: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF INTERIOR
 HANDRAILS AND GUARDRAIL AND FOR BALCONY GUARDRAIL
 SHOWING COMPLIANCE WITH TABLE R301.5, SEC. R311.7.8 AND
 SEC. R312.1 FBC-RESIDENTIAL.
  
 6-OK.
 7-OK.
 8- OK.
 9- OK.
 9- OK.
 10- OK.
 11- OK.
 12- OK.
  
 13- SECOND FLOOR FRAMING PLAN ON SHEET S-2:
  
 ORIGINAL COMMENT:
 PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR RED IRON
 STEEL BUCKET SUPPORTING NEW 2 PLY GIRDER TRUSSES (TWO
 TRUSS GIRDERS. SEE PLAN FOR LOCATIONS). CLEARLY SPECIFY
 BUCKET SIZE AND FASTENERS. SEC. R301.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 NO CLEAR ON BUCKET MATERIAL, SIZE AND FASTENERS.
 SPECIFICATIONS ON BUCK DETAIL ON SAME SHEET AND
 SPECIFICATIONS ON FLOOR FRAMING PLAN DON'T MATCH.
 CLARIFY AND REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 14- OK.
 15- OK.
  
 16-DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVAL FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS.)
 A)HARDIE PLANK SIDING AS SPECIFIED ON PLANS.
 B)EXTERIOR DOOR. DESIGN PRESSURES ON PLASTPRO DOOR
 FL17347.15 SUBMITTED DON'T MEET THE CALCULATED DESIGN
 PRESSURES. ALSO, CLARIFY WHERE IS THIS DOOR GOING TO BE
 INSTALLED.
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
 D)COLONIAL SHUTTERS A SHOWN ON PLANS AND PROVIDE
 INSTALLATION SCHEDULE.
 E)ROOFING UNDERLAYMENT SPECIFIED ON ONE & TWO STORY
 WALL SECTIONS.
 F)GABLE VENTS SHOWN ON PLANS.
 G)METAL ROOFING.
 H)FRENCH DOORS.
 I)HORIZONTAL ROLLER WINDOWS.
 J)ENTRY DOORS
 K) OVERHEAD GARAGE DOOR.
  
 17-ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 18- ENERGY CALCULATIONS:
 ORIGINAL COMMENT:
 A)IT LOOKS LIKE THE ENERGY CALCULATIONS ARE DONE FOR
 THE ENTIRE HOUSE (EXISTING AND PROPOSED). A/C SQUARE
 FOOTAGE SHOWN ON ITEM #6 IS ONLY FOR THE TWO STORY
 ADDITION. REVISE CLARIFY AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 (REVISED WILL NEED TO BE SIGNED BY ARCHITECT AS DONE
 WITH THIS SUBMITTAL).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B)OK.
 C)OK.
  
 ORIGINAL COMMENT:
 D)REVISE ITEM #9(A). THERE IS NO RAISED FLOOR IN THIS
 HOUSE. RAISED FLOOR APPLIES WHEN THERE IS A NON A/C
 SPACE BELOW. FIRST FLOOR IS AIR CONDITIONED. REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 E)REVISE ITEM #11(A). ATTIC AREA IS NOT 2992 S.F.
 COORDINATE WITH ITEM #18(A) ABOVE AND REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 F)OK.
 G)OK.
  
 ORIGINAL COMMENT:
 H)REVISE THE ATTIC VENT RATIO ON PAGE 2. TYPICALLY, THE
 RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL.
 OR PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. NOTE: ARCHITECT OF RECORD NEEDS TO REVISE PLANS
 PRIOR TO SUBMITTAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 I)DOORS INFORMATION ON PAGE 3 IS INCORRECT. NOTE: DOORS
 TO BE CONSIDERED ARE ONLY THE DOORS SEPARATING THE
 NON-A/C AREAS FROM A/C AREAS. OVERHEAD GARAGE DOOR IS
 NOT CONSIDERED. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC- ENERGY CONSERVATION.
 ALSO, CLARIFY WHERE IS THE OTHER 2X7 INSULATED DOOR
 LOCATED?. PLANS DON'T SHOW ANY INSULATED DOOR ON THE
 WEST SIDE. REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 J)REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 K)OK.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]