2021-12-15 16:21:10 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21090688 |
| |
| NOTE: |
| SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1- LOT DRAINAGE |
| PROVIDE COMPLETE DRAINAGE PLAN SHOWING COMPLIANCE WITH |
| THE FOLLOWING: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 |
| CITY AMENDMENTS. |
| SEC. 110.9 CITY AMENDMENTS. |
| NOTE: PROPOSED ADDITIONS ARE TO CLOSE TO THE NEIGHBOR |
| ON THE EAST SIDE. DRAINAGE PLAN TO SHOW THE EXISTING |
| AND PROPOSED GRADE ELEVATIONS SHOWING HOW KEEPING WATER |
| AWAY FROM ADJACENT PROPERTIES. |
| |
| 2- BEDROOM EGRESS WINDOWS: |
| A)ADDITION: PROVIDE COMPLETE WINDOW SCHEDULE. NEED TO |
| VERIFY COMPLIANCE WITH BEDROOM WINDOW EGRESS CLEAR |
| OPENINGS. SEC. R310.2.1 FBC-RESIDENTIAL. |
| |
| B) BEDROOM #2: CLEARLY SPECIFY TYPE AND SIZE OF |
| EXISTING WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOW |
| TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF |
| SEC. 702.5 FBC-EXISTING BUILDING. |
| |
| 3- NEW DOUBLE ENTRY DOOR DOESN'T COMPLY WITH THE MIN. |
| CLEAR WIDTH OF 32" AS REQUIRED BY SEC. R311.2 |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| NOTE: PROVIDE COMPLETE DOOR SCHEDULE. |
| |
| 4- PROVIDE COMPLETE DOOR SCHEDULE. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF INTERIOR HANDRAILS AND GUARDRAIL AND |
| FOR BALCONY GUARDRAIL SHOWING COMPLIANCE WITH TABLE |
| R301.5, SEC. R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL. |
| NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE |
| DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC. |
| R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS |
| THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW |
| PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED |
| BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL |
| TO THIS OFFICE. |
| |
| 6-PROVIDE FIRE RATING SPECIFICATIONS FOR THE SWING DOOR |
| LEADING FROM THE GARAGE TO THE MAIN HOUSE AS REQUIRED |
| BY SEC. R302. 5.1 FBC-RESIDENTIAL. |
| |
| 7-WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND |
| FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN |
| OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE |
| FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL. |
| NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND |
| FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL |
| PROTECTION IF REQUIRED. |
| |
| 8-DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD LOADS |
| FOR SECOND FLOOR AND ROOF. CLEARLY SPECIFY SECOND FLOOR |
| LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS) AND ROOF |
| LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS), INCLUDING |
| THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 |
| FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G". |
| NOTE: ATTIC ACCESS ON THE SECOND FLOOR SHOWS A LADDER. |
| IT IS ASSUMED THIS ATTIC IS GOING TO BE USED FOR |
| STORAGE. SEE ROOF FAMING PLAN. |
| |
| 9- ARCHITECT OF RECORD TO PROVIDE SPECIFICATIONS |
| SHOWING HOW COMPLYING WITH THE NEW 2020 CODE |
| REQUIREMENT FOR ROOFING UNDERLAYMENT. SEC. R905.1.1.1 |
| FBC-RESIDENTIAL. |
| NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. |
| NOTE: ONE WALL SECTION SPECIFIES METAL ROOF AND THE |
| OTHER WALL SECTION SPECIFIES SHINGLES. REVISE AS |
| REQUIRED TO MATCH. |
| |
| 10- REVISE ROOF SHEATHING NAILING SPACING. ROOF |
| SHEATHING NEEDS TO BE NAILED AT 4 INCHES O.C. IN THE |
| FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND |
| TABLE R803.2.3.1 FBC-RESIDENTIAL. |
| NOTE: REVISE SPECIFICATIONS ON ALL PLANS AND WALL |
| SECTIONS TO AVOID CONFLICTS/DELAYS. |
| |
| 11- PLYWOOD SHEATHING NAILING SCHEDULE-GABLE ON SHEET |
| S-2 AND S-3: |
| A)DESIGN PRESSURES SPECIFIED ON THE PLYWOOD SHEATHING |
| NAILING SCHEDULE-GABLE ON SHEET S-2 AND S-3 ARE |
| INCORRECT. SEE TABLE R301.2(2) FBC-RESIDENTIAL AND |
| TABLE R301.2(3)FBC-RESIDENTIAL |
| FOR CORRECT DESIGN PRESSURES OR PROVIDE ACTUAL |
| CALCULATIONS. |
| NOTE: REVISE ROOF SHEATHING DETAIL ON SHEET S.6 TO |
| MATCH TO AVOID CONFLICTS/DELAYS. |
| |
| B) REVISE THE "A" DIMENSION SHOWN ON THE GABLE PLAN. |
| DIMENSION "A" IS 4'-0" MIN. AS REQUIRED BY FIGURE |
| R301.2(7) FBC-RESIDENTIAL. |
| |
| 12- TWO STORY WALL SECTION: THERE IS A CONCERN ABOUT |
| THE SUPPORT OF THE SECOND FLOOR TRUSSES. |
| SPECIFICATIONS FOR THE ATTACHMENT OF THE STRUCTURAL |
| LEDGER SUPPORTING THE FLOOR TRUSSES |
| SHOWN ON THE TWO STORY WALL SECTION AND THE SECOND |
| FLOOR FRAMING PLAN DON'T MATCH. CLEARLY SPECIFY ANCHOR |
| TYPE SIZE AND SPACING AND REVISE AS REQUIRED TO MATCH. |
| ALSO, PROVIDE CALCULATIONS SHOWING THAT THE SPECIFIED |
| FASTENER SIZE AND SPACING IS ADEQUATE TO SUPPORT THE |
| STRUCTURAL LOAD. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| NOTE: PROVIDE COMPLETE FASTENER SPECIFICATIONS, |
| INCLUDING REQUIRED FASTENER EMBEDMENT INTO THE |
| STRUCTURAL WALL. |
| |
| 13- SECOND FLOOR FRAMING PLAN ON SHEET S-2: |
| A)PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR RED |
| IRON STEEL BUCKET SUPPORTING NEW 2 PLY GIRDER TRUSSES |
| (TWO TRUSS GIRDERS. SEE PLAN FOR LOCATIONS). CLEARLY |
| SPECIFY BUCKET SIZE AND FASTENERS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| B)PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR |
| CONNECTION TO THE MASONRY WALL OF 2 PLY GIRDER TRUSS AT |
| STAIRWAY OPENING. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 14- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR NEW |
| RAKED BEAMS. BEAM SCHEDULE DOESN'T PROVIDE THIS |
| INFORMATION. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 15- PROVIDE SURVEY SHOWING THE PROPOSED BUILDING AND |
| THE SETBACKS. SEC. 107.3.5.3 CITY AMENDMENTS. |
| SEC. 107.2.5 CITY AMENDMENTS. |
| |
| 16-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS.) |
| |
| A)HARDIE PLANK SIDING AS SPECIFIED ON PLANS. |
| |
| B)EXTERIOR DOOR. DESIGN PRESSURES ON PLASTPRO DOOR |
| FL17347.15 SUBMITTED DON'T MEET THE CALCULATED DESIGN |
| PRESSURES. ALSO, CLARIFY WHERE IS THIS GOING TO BE |
| INSTALLED. |
| |
| C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| TO AVOID DELAYS/CONFLICTS). |
| |
| D)COLONIAL SHUTTERS A SHOWN ON PLANS AND PROVIDE |
| INSTALLATION SCHEDULE. |
| |
| E)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| |
| F)GABLE VENTS SHOWN ON PLANS. |
| |
| 17-ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 18- ENERGY CALCULATIONS: |
| A)IT LOOKS LIKE THE ENERGY CALCULATIONS ARE DONE FOR |
| THE ENTIRE HOUSE (EXISTING AND PROPOSED). A/C SQUARE |
| FOOTAGE SHOWN ON ITEM #6 IS ONLY FOR THE TWO STORY |
| ADDITION. REVISE CLARIFY AS REQUIRED. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| (REVISED WILL NEED TO BE SIGNED BY ARCHITECT AS DONE |
| WITH THIS SUBMITTAL). |
| NOTE: A/C EQUIPMENT LOAD CALCULATIONS NEED TO BE |
| REVISED ACCORDINGLY. |
| |
| B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER'S NAME, BUILDER'S NAME. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| C)NUMBER OF BEDROOMS IS INCORRECT. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| D)REVISE ITEM #9(A). THERE IS NO RAISED FLOOR IN THIS |
| HOUSE. RAISED FLOOR APPLIES WHEN THERE IS A NON A/C |
| SPACE BELOW. FIRST FLOOR IS AIR CONDITIONED. REVISE AS |
| REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| E)REVISE ITEM #11(A). ATTIC AREA IS NOT 2992 S.F. |
| COORDINATE WITH ITEM #18(A) ABOVE AND REVISE AS |
| REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| F)REVISE ROOF TYPE SPECIFIED ON PAGE 2. THERE IS NO HIP |
| ROOF. SEE PLANS AND REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| G)REVISE ROOF MATERIAL SPECIFIED ON PAGE 2. THERE ARE |
| NO SHINGLES. SEE PLANS AND REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| H)REVISE THE ATTIC VENT RATIO ON PAGE 2. TYPICALLY, THE |
| RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL. |
| OR PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE |
| COMPLETE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH |
| THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC. |
| R806.2. NOTE: ARCHITECT OF RECORD NEEDS TO REVISE PLANS |
| PRIOR TO SUBMITTAL. |
| |
| I)DOORS INFORMATION ON PAGE 3 IS INCORRECT. NOTE: DOORS |
| TO BE CONSIDERED ARE ONLY THE DOORS SEPARATING THE |
| NON-A/C AREAS FROM A/C AREAS. OVERHEAD GARAGE DOOR IS |
| NOT CONSIDERED. REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| FBC- ENERGY CONSERVATION. |
| ALSO, CLARIFY WHERE IS THE OTHER 2X7 INSULATED DOOR |
| LOCATED?. PLANS DON'T SHOW ANY INSULATED DOOR ON THE |
| WEST SIDE. REVISE AS REQUIRED. |
| |
| J)REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| K)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |