Plan Review Notes
Plan Review Notes For Permit 21090688
Permit Number 21090688
Review Stop B
Sequence Number 1
Notes
Date Text
2021-12-15 16:21:10RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21090688
  
 NOTE:
 SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- LOT DRAINAGE
 PROVIDE COMPLETE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 THE FOLLOWING: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5
 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: PROPOSED ADDITIONS ARE TO CLOSE TO THE NEIGHBOR
 ON THE EAST SIDE. DRAINAGE PLAN TO SHOW THE EXISTING
 AND PROPOSED GRADE ELEVATIONS SHOWING HOW KEEPING WATER
 AWAY FROM ADJACENT PROPERTIES.
  
 2- BEDROOM EGRESS WINDOWS:
 A)ADDITION: PROVIDE COMPLETE WINDOW SCHEDULE. NEED TO
 VERIFY COMPLIANCE WITH BEDROOM WINDOW EGRESS CLEAR
 OPENINGS. SEC. R310.2.1 FBC-RESIDENTIAL.
  
 B) BEDROOM #2: CLEARLY SPECIFY TYPE AND SIZE OF
 EXISTING WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOW
 TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS OF
 SEC. 702.5 FBC-EXISTING BUILDING.
  
 3- NEW DOUBLE ENTRY DOOR DOESN'T COMPLY WITH THE MIN.
 CLEAR WIDTH OF 32" AS REQUIRED BY SEC. R311.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 NOTE: PROVIDE COMPLETE DOOR SCHEDULE.
  
 4- PROVIDE COMPLETE DOOR SCHEDULE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 5- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF INTERIOR HANDRAILS AND GUARDRAIL AND
 FOR BALCONY GUARDRAIL SHOWING COMPLIANCE WITH TABLE
 R301.5, SEC. R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: IF THIS IS A DEFERRED SUBMITTAL, THEN SPECIFY THE
 DESIGN GUIDELINES REQUIRED BY TABLE R301.5, SEC.
 R311.7.8 AND SEC. R312.1 AND CLEARLY SPECIFY ON PLANS
 THAT SHOP DRAWINGS NEED TO BE SUBMITTED FOR REVIEW
 PRIOR TO CONSTRUCTION. ALL SHOP DRAWINGS TO BE REVIEWED
 BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO SUBMITTAL
 TO THIS OFFICE.
  
 6-PROVIDE FIRE RATING SPECIFICATIONS FOR THE SWING DOOR
 LEADING FROM THE GARAGE TO THE MAIN HOUSE AS REQUIRED
 BY SEC. R302. 5.1 FBC-RESIDENTIAL.
  
 7-WINDOW FALL PROTECTION SHALL BE PROVIDED ON SECOND
 FLOOR WINDOWS WHERE THE TOP OF THE WINDOW SILL OF AN
 OPERABLE WINDOW IS LOCATED LESS THAN 24" ABOVE THE
 FINISHED FLOOR . SEC. R312.2 FBC RESIDENTIAL.
 NOTE: CLEARLY INDICATE THE WINDOW SILL HEIGHT OF SECOND
 FLOOR WINDOWS AND SPECIFY TYPE OF WINDOW FALL
 PROTECTION IF REQUIRED.
  
 8-DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD LOADS
 FOR SECOND FLOOR AND ROOF. CLEARLY SPECIFY SECOND FLOOR
 LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS) AND ROOF
 LIVE AND DEAD LOADS (TOP AND BOTTOM CHORDS), INCLUDING
 THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5
 FBC-RESIDENTIAL. SEE FOOTNOTES "B" AND "G".
 NOTE: ATTIC ACCESS ON THE SECOND FLOOR SHOWS A LADDER.
 IT IS ASSUMED THIS ATTIC IS GOING TO BE USED FOR
 STORAGE. SEE ROOF FAMING PLAN.
  
 9- ARCHITECT OF RECORD TO PROVIDE SPECIFICATIONS
 SHOWING HOW COMPLYING WITH THE NEW 2020 CODE
 REQUIREMENT FOR ROOFING UNDERLAYMENT. SEC. R905.1.1.1
 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001.
 NOTE: ONE WALL SECTION SPECIFIES METAL ROOF AND THE
 OTHER WALL SECTION SPECIFIES SHINGLES. REVISE AS
 REQUIRED TO MATCH.
  
 10- REVISE ROOF SHEATHING NAILING SPACING. ROOF
 SHEATHING NEEDS TO BE NAILED AT 4 INCHES O.C. IN THE
 FIELD AND EDGES AS REQUIRED BY SEC. R803.2.3.1 AND
 TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS ON ALL PLANS AND WALL
 SECTIONS TO AVOID CONFLICTS/DELAYS.
  
 11- PLYWOOD SHEATHING NAILING SCHEDULE-GABLE ON SHEET
 S-2 AND S-3:
 A)DESIGN PRESSURES SPECIFIED ON THE PLYWOOD SHEATHING
 NAILING SCHEDULE-GABLE ON SHEET S-2 AND S-3 ARE
 INCORRECT. SEE TABLE R301.2(2) FBC-RESIDENTIAL AND
 TABLE R301.2(3)FBC-RESIDENTIAL
 FOR CORRECT DESIGN PRESSURES OR PROVIDE ACTUAL
 CALCULATIONS.
 NOTE: REVISE ROOF SHEATHING DETAIL ON SHEET S.6 TO
 MATCH TO AVOID CONFLICTS/DELAYS.
  
 B) REVISE THE "A" DIMENSION SHOWN ON THE GABLE PLAN.
 DIMENSION "A" IS 4'-0" MIN. AS REQUIRED BY FIGURE
 R301.2(7) FBC-RESIDENTIAL.
  
 12- TWO STORY WALL SECTION: THERE IS A CONCERN ABOUT
 THE SUPPORT OF THE SECOND FLOOR TRUSSES.
 SPECIFICATIONS FOR THE ATTACHMENT OF THE STRUCTURAL
 LEDGER SUPPORTING THE FLOOR TRUSSES
 SHOWN ON THE TWO STORY WALL SECTION AND THE SECOND
 FLOOR FRAMING PLAN DON'T MATCH. CLEARLY SPECIFY ANCHOR
 TYPE SIZE AND SPACING AND REVISE AS REQUIRED TO MATCH.
 ALSO, PROVIDE CALCULATIONS SHOWING THAT THE SPECIFIED
 FASTENER SIZE AND SPACING IS ADEQUATE TO SUPPORT THE
 STRUCTURAL LOAD. SEC. 107.2.1.2 CITY AMENDMENTS. SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: PROVIDE COMPLETE FASTENER SPECIFICATIONS,
 INCLUDING REQUIRED FASTENER EMBEDMENT INTO THE
 STRUCTURAL WALL.
  
 13- SECOND FLOOR FRAMING PLAN ON SHEET S-2:
 A)PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR RED
 IRON STEEL BUCKET SUPPORTING NEW 2 PLY GIRDER TRUSSES
 (TWO TRUSS GIRDERS. SEE PLAN FOR LOCATIONS). CLEARLY
 SPECIFY BUCKET SIZE AND FASTENERS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B)PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR
 CONNECTION TO THE MASONRY WALL OF 2 PLY GIRDER TRUSS AT
 STAIRWAY OPENING. SEC. R301.1 FBC-RESIDENTIAL.
  
 14- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS FOR NEW
 RAKED BEAMS. BEAM SCHEDULE DOESN'T PROVIDE THIS
 INFORMATION. SEC. R301.1 FBC-RESIDENTIAL.
  
 15- PROVIDE SURVEY SHOWING THE PROPOSED BUILDING AND
 THE SETBACKS. SEC. 107.3.5.3 CITY AMENDMENTS.
 SEC. 107.2.5 CITY AMENDMENTS.
  
 16-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS.)
  
 A)HARDIE PLANK SIDING AS SPECIFIED ON PLANS.
  
 B)EXTERIOR DOOR. DESIGN PRESSURES ON PLASTPRO DOOR
 FL17347.15 SUBMITTED DON'T MEET THE CALCULATED DESIGN
 PRESSURES. ALSO, CLARIFY WHERE IS THIS GOING TO BE
 INSTALLED.
  
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
  
 D)COLONIAL SHUTTERS A SHOWN ON PLANS AND PROVIDE
 INSTALLATION SCHEDULE.
  
 E)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 F)GABLE VENTS SHOWN ON PLANS.
  
 17-ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 18- ENERGY CALCULATIONS:
 A)IT LOOKS LIKE THE ENERGY CALCULATIONS ARE DONE FOR
 THE ENTIRE HOUSE (EXISTING AND PROPOSED). A/C SQUARE
 FOOTAGE SHOWN ON ITEM #6 IS ONLY FOR THE TWO STORY
 ADDITION. REVISE CLARIFY AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 (REVISED WILL NEED TO BE SIGNED BY ARCHITECT AS DONE
 WITH THIS SUBMITTAL).
 NOTE: A/C EQUIPMENT LOAD CALCULATIONS NEED TO BE
 REVISED ACCORDINGLY.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)NUMBER OF BEDROOMS IS INCORRECT. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 D)REVISE ITEM #9(A). THERE IS NO RAISED FLOOR IN THIS
 HOUSE. RAISED FLOOR APPLIES WHEN THERE IS A NON A/C
 SPACE BELOW. FIRST FLOOR IS AIR CONDITIONED. REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)REVISE ITEM #11(A). ATTIC AREA IS NOT 2992 S.F.
 COORDINATE WITH ITEM #18(A) ABOVE AND REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)REVISE ROOF TYPE SPECIFIED ON PAGE 2. THERE IS NO HIP
 ROOF. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)REVISE ROOF MATERIAL SPECIFIED ON PAGE 2. THERE ARE
 NO SHINGLES. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)REVISE THE ATTIC VENT RATIO ON PAGE 2. TYPICALLY, THE
 RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL.
 OR PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. NOTE: ARCHITECT OF RECORD NEEDS TO REVISE PLANS
 PRIOR TO SUBMITTAL.
  
 I)DOORS INFORMATION ON PAGE 3 IS INCORRECT. NOTE: DOORS
 TO BE CONSIDERED ARE ONLY THE DOORS SEPARATING THE
 NON-A/C AREAS FROM A/C AREAS. OVERHEAD GARAGE DOOR IS
 NOT CONSIDERED. REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC- ENERGY CONSERVATION.
 ALSO, CLARIFY WHERE IS THE OTHER 2X7 INSULATED DOOR
 LOCATED?. PLANS DON'T SHOW ANY INSULATED DOOR ON THE
 WEST SIDE. REVISE AS REQUIRED.
  
 J)REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 K)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  