2022-02-07 14:55:57 | RESIDENTIAL (R3) ADDITION, ALTERATION BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21090681 |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| 1- OK. VARIANCE APPROVED. |
| 2- OK. |
| 3- OK. |
| |
| 4-PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. 1101.1 |
| FBC-EXISTING BUILDING AND SEC. R401.4 FBC-RESIDENTIAL. |
| NOTE: CHECK ENGINEER'S RECOMMENDATIONS TO SEE IF |
| STRUCTURAL REVISIONS ARE REQUIRED. |
| |
| COMMENTS FOR GARAGE BUILDING: |
| 5-16 GARAGE WILL BE SUBMITTED LATER UNDER A SEPARATE |
| PERMIT. |
| |
| MAIN HOUSE: |
| 17- OK. |
| 18- OK. |
| 19- OK. |
| |
| 20- ROOF VENTILATION |
| PLANS REVISED FOR UNVENTED ATTIC. NEED TO PROVIDE ICC |
| EVALUATION REPORT FOR30 FOAM INSULATION REVIEWED-BY THE |
| ARCH. OF RECORD. |
| |
| 21- ROOF FRAMING PLAN: IF EXISTING TRUSSES ARE CUT OR |
| ALTERED TO ALLOW FOR NEW ROOF FRAMING, THE ENGINEERED |
| DETAILS ARE REQUIRED. |
| |
| 22-OK. |
| |
| 23-ALL ROOFING, WINDOWS, DOORS AND MULLIONS PRODUCT |
| APPROVALS ARE DEFERRED. SUBMIT THEM (REVIEWED BY |
| ARCHITECT) FOR REVIEW PRIOR TO INSTALLATION TO AVOID |
| CONFLICTS/DELAYS. |
| NOTE: WINDOW MULLION. CLEARLY SPECIFY MULLION TO SIZE |
| TO VERIFY DESIGN PRESSURES. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |