Plan Review Notes
Plan Review Notes For Permit 21090681
Permit Number 21090681
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-20 15:13:591ST REVIEW FBC-2020 RES.
 PERMIT- 21090681
 10/20/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MP-1G: NON-COMPLIANT WET VENTS FOR THE
 BATHROOMS. A) NOT MORE THAN ONE WET-VENTED FIXTURE
 DRAIN (WC, SHOWER) SHALL DISCHARGE UPSTREAM OF THE DRY
 VENT FOR THE LAV- SECTION P3108.2.1 FBC P. B) THE
 FIXTURE DRAIN FOR THE BAR SINK SHALL NOT CONNECT TO THE
 WET VENT FOR THE GARAGE BATHROOM- SECTION P3108.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  