2021-11-30 13:10:54 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21090649 |
| ADD: 3640 WHITEHALL DR. # 205 |
| CONT: REECE BUILDERS EAST COAST DIVISION / CGC1527975 |
| TEL: 407-989-8701 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. NOV. 30TH/ 2021 |
| ACTION: DENIED |
| |
| 1) REECE BUILDERS FLOOR PLAN NEEDS TO SHOW COMPLIANCE |
| WITH 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION SECTION |
| CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR |
| (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL |
| NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS. |
| PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE |
| NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS |
| DRAWN. |
| |
| 2) MISSING 2020 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 2.2. RISK CATEGORY. |
| |
| 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| |
| 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. ASCE 7-16 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| CONVERSION VULT TO VASD. |
| |
| 3) PROVIDE A SIGNED AND SEALED ENGINEERING SHEET FOR |
| WIND PRESSURES. CONTRACTORS CAN ONLY PROVIDE PRESSURES |
| FOR A ONE- & TWO-FAMILY DWELLING FROM THE 2020 |
| RESIDENTIAL CODE TABLE R301.2(2). |
| |
| 4) WITHOUT THE MISSING DATA FROM COMMENTS 2 & 3 THIS |
| REVIEW CAN NOT BE FULLY COMPLETED. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| FROM CITY HALL. |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |