 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL1654-R27 HAS BEEN
 REVISED TO FL1654-R28. PLEASE PROVIDE A COMPLETE SET.
 INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION
 INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R27 SELECTED SYSTEM NO. W-209 DO NOT
 MEET THE EXPOSURE CATEGORY D; ZONE 2 & 3 MINIMUM DESIGN
 PRESSURE REQUIREMENT. PLEASE SELECT SYSTEM NO. THAT
 MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND
 SEALED ENGINEERED NAILING CALCULATIONS FOR ZONE 2 & 3.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. THE
 CORRECT EXPOSURE FOR THIS ADDRESS IS EXPOSURE D
 (-131.42).
 3. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR
 THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL
 HEIGHT(S).
 4. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT
 COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL
 AND CHAPTER 11 OF THE 2020 FBC-PLUMBING.
 5. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S) & MEAN
 ROOF HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  