Plan Review Notes For Permit 21090582 |
Permit Number |
21090582 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-10-16 09:44:12 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FBC 107 SCOPE NOT CLEAR. IT APPEARS THAT APPLICANT | | PROPOSES TO REMOVE A RATED DOOR IN THE RATED CORRIDOR. | | REMOVE FROM THE SCOPE AS THIS AFFECTS THE LIFE SAFETY | | OF OTHER UNITS. | | | | 2. FBC 107 SCOPE NOT CLEAR. IT APPEARS THAT A FIRE | | RATED WALL IS BEING REMOVED. REVISE PLAN TO CLARIFY | | THAT TWO UNITS ARE BEING COMBINED, OR REMOVE THIS FROM | | SCOPE OF WORK AND SUBMIT A SECOND PERMIT SO YOU HAVE | | ONE INTERIOR DEMO PERMIT FOR EACH UNIT. | | | | 3. IF YOU WISH TO COMBINE THE UNITS, PLEASE CONTACT THE | | ENGINEERING DEPARTMENT REGARDING A UNITY OF TITLE. | | | | |
|