Plan Review Notes
Plan Review Notes For Permit 21090570
Permit Number 21090570
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-19 11:42:4310/19/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW. THE MAXIMUM
 FLOW OF THE PUMP FROM ITS PUMP CURVE IS NO LONGER
 ALLOWED TO BE USED IN DETERMINING THE MAXIMUM SYSTEM
 FLOW RATE PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9,
 4.4.9.1. THE 2013 EDITION ADDRESSES THE FLOW RATE IN
 GALLONS PER MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM
 SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED MAXIMUM
 FLOW RATE OF THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN
 COVER). THE TDH CALCULATIONS MUST INCLUDE ALL THE
 SYSTEM COMPONENTS, INCLUDING SUCTION AND RETURN PIPING,
 FITTINGS, VALVES, HEATER, AND FILTER. ALL SYSTEM
 COMPONENTS EXCEPT THE PUMP.
  
 2. WOULD YOU PLEASE SUBMIT THE POOL PUMP CURVE AND
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2015 SECS.
 4.4.9, 4.4.9.1.
  
 3. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY
 INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT
 COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR
 OTHER MEANS PROVEN TO REDUCE HEAT LOSS PER THE 2020
 FBC- ENERGY- SEC. R 403.10.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  