2021-09-16 16:49:50 | 1ST REVIEW FBC-2020 RES. BUILDING. |
| PERMIT- 21090547 |
| 9/16/21 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE MIAMI-DADE NOA 18-0919.07 FOR THE FLAT ROOF |
| CONTAINED WITH THE CALCULATIONS MUST BE PROPERLY NAMED |
| AND SUBMITTED AS A SEPARATE DOCUMENT. THE NOA SUBMITTAL |
| SHALL INCLUDE THE COVER PAGE, PAGES 2-7, THE SELECTED |
| SYSTEM PAGE 21, AND THE LIMITATIONS OF USE PAGE 27- FAC |
| RULE 9N-3 & SECTION 107.2.1 WPB. |
| |
| 2) PLEASE ADD THE SLOPE OF THE TILE ROOF ON THE SKETCH. |
| A COMPLETE REVIEW OF THE TILE ROOF CANNOT BE COMPLETED |
| WITHOUT THE ROOF SLOPE INFORMATION- R905.3, FAC RULE |
| 9N-3, AND SECTION 107.2.1 WPB. |
| |
| 3) MIAMI-DADE NOA #21-0107.04 TILE: PLEASE MARKUP |
| TABLES 4, 5, 6 & 7 TO SHOW THE FASTENER TYPE, DECK |
| PLYWOOD THICKNESS, AND ADHESIVE SYSTEM (IF APPLICABLE). |
| PLEASE NOTE THAT INSTALLATIONS USING ADHESIVE REQUIRE |
| SUBMITTAL OF A CURRENT MIAMI-DADE NOA OR FL. PRODUCT |
| APPROVAL- FAC RULE 9N-3, AND SECTION 107.2.1 WPB. |
| PLEASE NOTE THAT THE APPLICABLE DETAILS ON THE ADHESIVE |
| PRODUCT APPROVAL OR NOA MUST BE MARKED OR HIGHLIGHTED. |
| |
| 4) MIAMI-DADE NOA #17-0614.22 UNDERLAYMENT: PLEASE |
| CIRCLE OR HIGHLIGHT PRODUCT SELECTION ON PAGE 2, THE |
| INSTALLATION PROCEDURE AND DECK TYPE ON PAGE 4, AND THE |
| APPLICABLE GENERAL LIMITATIONS ON PAGE 5. 6, 7 & 8. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |