Plan Review Notes
Plan Review Notes For Permit 21090534
Permit Number 21090534
Review Stop B
Sequence Number 1
Notes
Date Text
2021-10-10 08:56:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE THE PLAN TO SHOW THAT DOOR #4 (ELECTRIC ROOM)
 IS NOT REQUIRED TO HAVE PANIC DEVICES, FBC B 1010.1.10,
 OR REVISE SUBMITTAL TO PROPOSE PANIC DEVICES ON THIS
 PAIR OF DOORS:
  
 ELECTRICAL ROOMS WITH EQUIPMENT RATED 1,200 AMPERES OR
 MORE AND OVER 6 FEET (1829 MM) WIDE, AND THAT CONTAIN
 OVERCURRENT DEVICES, SWITCHING DEVICES OR CONTROL
 DEVICES WITH EXIT OR EXIT ACCESS DOORS, SHALL BE
 EQUIPPED WITH PANIC HARDWARE OR FIRE EXIT HARDWARE. THE
 DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL.
  
 2. FOR DOORS 2, 5, AND 6 - REVISE PLAN TO CLARIFY THAT
 THESE DOORS ARE NOT PART OF THE MEANS OF EGRESS FOR
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OF 50 OR MORE,
 FBC B 1010.1.10, OR REVISE SUBMITTAL TO PROPOSE PANIC
 HARDWARE:
  
 SWINGING DOORS SERVING . . . ROOMS OR SPACES WITH AN
 OCCUPANT LOAD OF 50 OR MORE IN A GROUP A ... OCCUPANCY
 SHALL NOT BE PROVIDED WITH A LATCH OR LOCK OTHER THAN
 PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
  
  