Plan Review Notes
Plan Review Notes For Permit 21090525
Permit Number 21090525
Review Stop B
Sequence Number 2
Notes
Date Text
2021-11-23 11:15:02RESIDENTIAL (R3) SHUTTERS, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21090525
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE.
 SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED.
 ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION
 SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE
 REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 BASED ON SHUTTERS PRODUCT APPROVAL FL12549-R7 THE
 INSTALLATION SCHEDULE NEEDS TO BE REVISED. SEC. 107.2.1
 CITY AMENDMENTS:
 A) 2" ITW TAPCON DOESN'T PROVIDE 1-3/4" EMBEDMENT INTO
 CONCRETE AS REQUIRED BY ANCHOR SCHEDULE ON SHEET 11 OF
 12.
 B) DESIGN PRESSURES DON'T MATCH THOSE SHOWN ON THE
 DESIGN PRESSURES CHART SUBMITTED.
 NOTE: BASED ON THE DESIGN PRESSURES CHART SUBMITTED
 NEED TO USE THE 60PSF DESIGN PRESSURES TO DETERMINE THE
 ANCHOR SPACING.
 C) BOTTOM OF OPENING IS CONCRETE BLOCK. NEED TO USE THE
 CONCRETE BLOCK ANCHOR SCHEDULE. REVISE ANCHOR SPACING
 AS REQUIRED.
 NOTE: BASED ON ON THE ANCHOR SCHEDULE ON SHEET 12 OF 12
 IT LOOKS LIKE THE 1/4" ITW TAPCON CAN NOT BE USED.
 REVISE AS REQUIRED. NEED TO USE ANOTHER FASTENER TYPE.
  
 NOTE:
 MINIMUM EDGE DISTANCE EXCLUDES STUCCO FINISH.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712