Plan Review Notes
Plan Review Notes For Permit 21090525
Permit Number 21090525
Review Stop B
Sequence Number 1
Notes
Date Text
2021-10-25 15:46:15RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21090525
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE.
 SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED.
 ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION
 SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE
 REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
  
 2- RAMMS ENGINEERING, INC. DESIGN PRESSURES
 CALCULATIONS SUBMITTED:
 A) CALCULATIONS NEED THE ORIGINAL SEAL AND SIGNATURE OF
 THE ENGINEER AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES WHEN SUBMITTING DOCUMENTS/PLANS FOR PUBLIC
 RECORDS.
 NOTE: SUBMIT CALCULATIONS ELECTRONICALLY WITH
 ENGINEER'S DIGITAL SIGNATURE OR PROVIDE HARD COPY
 CALCULATIONS WITH ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE.
  
 B)CURRENT BUILDING CODE IS 2020 FBC NOT 2017. AND, 2020
 FBC REFERENCES THE ASCE 7-16 NOT ASCE 7-10. ENGINEER TO
 REVISE CALCULATIONS.
 CHAPTER 553 F.S.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712