2021-10-25 15:46:15 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21090525 |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS |
| REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE |
| DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE. |
| SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED. |
| ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION |
| SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE |
| REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| |
| 2- RAMMS ENGINEERING, INC. DESIGN PRESSURES |
| CALCULATIONS SUBMITTED: |
| A) CALCULATIONS NEED THE ORIGINAL SEAL AND SIGNATURE OF |
| THE ENGINEER AS REQUIRED BY CHAPTER 471 FLORIDA |
| STATUTES WHEN SUBMITTING DOCUMENTS/PLANS FOR PUBLIC |
| RECORDS. |
| NOTE: SUBMIT CALCULATIONS ELECTRONICALLY WITH |
| ENGINEER'S DIGITAL SIGNATURE OR PROVIDE HARD COPY |
| CALCULATIONS WITH ENGINEER'S ORIGINAL SEAL AND |
| SIGNATURE. |
| |
| B)CURRENT BUILDING CODE IS 2020 FBC NOT 2017. AND, 2020 |
| FBC REFERENCES THE ASCE 7-16 NOT ASCE 7-10. ENGINEER TO |
| REVISE CALCULATIONS. |
| CHAPTER 553 F.S. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |