Plan Review Notes For Permit 21090477 |
Permit Number |
21090477 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-09-25 08:35:21 | PLAN REVIEW / ELECTRICAL | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | PLANS EXAMINER II PX3169/SFP306 | | INSPECTOR BN4338 | | BUILDING OFFICIAL BU1635 | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | DEVELOPMENT SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | (561) 805-6726 | | [email protected] | | | | CODES IN EFFECT: | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | CHAPTER 1 ADMINISTRATION | | 2017 NEC | | | | 1ST REVIEW | | | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE SMOKE DETECTORS. IDENTIFY LOCATION ON FLOOR | | PLAN. | | R314.1 GENERAL. | | SMOKE ALARMS SHALL COMPLY WITH NFPA 72 AND SECTION | | R314. | | | | 2. ENERGY CODE ? LUMINAIRES: | | PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. | | FBC EC C405.1, R404.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|