Plan Review Notes
Plan Review Notes For Permit 21090401
Permit Number 21090401
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-09-13 15:07:19PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT.
  
  
 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED
 EGRESS
 DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS
 SHALL BE
 PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL
 LOCKING SYSTEMS
 RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED
 THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF
 THE ELECTRICAL
 LOCK IS AFFIXED TO THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY
 OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING
 CONDITIONS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE
 DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE
 POWER SUPPLY TO
 THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE
 DIRECTION
 OF EGRESS.
 (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY ELECTRICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  