2021-10-21 08:09:24 | 10/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET A1.0 |
| |
| A. IN THE BREAK ROOM 111 AND THE GALLERY AREA 115 SHOWS |
| A SINK, WOULD YOU PLEASE GIVE THE DIMESONS 30 INCHES BY |
| 48 INCHES PER THE 2020 FBC ACC SEC. 305 CLEAR FLOOR OR |
| GROUND SPACE. |
| |
| B. THERE IS AN ELEVATION OF THE BREAK ROOM 110 A-1, BUT |
| THE ELEVATION SHOWS THE COUNTER TO AT THREE FEET INCHES |
| MAXIMUM AND IT NEEDS TO BE AT 2 FEET 10 INCHES PER THE |
| 2020 FBC ACC SEC. 606.3. |
| |
| C. THE SINK IN THE GALLERY SHOWS A CLEAR FLOOR SPACE |
| BUT NO DETAIL FOR THE COUNTER HEIGHT; THIS SHOULD BE AT |
| 34 INCHES MAXIMUM PER THE 2020 FBC ACC SEC. 606.3. |
| WOULD YOU PLEASE PROVIDE DETAIL ON THIS PAGE OR GIVE A |
| REFERENCE PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| D. THERE IS A SAUNA IN ROOM 110, AND MECHANICAL IS |
| REQUESTING MANUFACTURERS SPECIFICATION. PLEASE PROVIDE |
| INFORMATION IF IT IS A STEAM UNIT AND NEEDS HOT WATER |
| OR A DRAIN PER THE WPB AMENDMENTS TO THE FBC SEC |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| |
| 2. ON SHEET P01; |
| |
| A. IT SHOWS SANITARY ON THE FLOOR. WOULD YOU PLEASE |
| SUBMIT A SLAB REPAIR DETAIL FOR REVIEW? SHOW THE WIDTH |
| OF THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO |
| BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH |
| INTO THE EXISTING SLAB, AND THE SPACING OF THE DOWELS |
| IN THE CENTER. THE REPAIR MAY ALSO INCLUDE TERMITE |
| TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER |
| OVER THE EARTH. A COPY OF THE TERMITE CERTIFICATE SHALL |
| BE ONSITE FOR A FINAL INSPECTION IF APPLICABLE. |
| |
| B. IT SHOWS A WASHING MACHINE THAT WILL REQUIRE A LINT |
| TRAP; PLEASE SUPPLY DETAILS OR NOTES PER THE 2020 FBC |
| SEC. 1003.6. A MODEL HLT-1176 IS USED A LOT IN OUR |
| MUNICIPALITY, AND YOU ARE WELCOME TO USE THIS ONE OR |
| ONE SIMILAR. HTTPS://STRIEMCO.COM/WP-CONTENT/UPLOADS/20 |
| 20/03/6010-6025-001-01-HLT-HLB.PDF . |
| |
| C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET? |
| |
| 3. ON SHEET P02; |
| |
| A. WOULD YOU PLEASE SHOW THE COLD WATER FOR THE |
| RESTROOMS AND THE WATER FOUNTAIN PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. IF COLD WATER EXISTS, PLEASE SHOW AND LABEL |
| IT. |
| |
| B. WOULD YOU PLEASE SHOW THE HAMMER ARRESTORS ON THE |
| WASHING MACHINE PER THE 2020 FBC P 604.9. |
| |
| C. WOULD YOU PLEASE PUT A NOTE NEXT TO THE WATER HEATER |
| FOR DETAIL ON SHEET P-4 PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| D. THERE ARE HOT WATER LINES IN THE GROUND AND NOT IN |
| CONDITION SPACE, SO THEY NEED TO BE INSULATED WITH A |
| MINIMUM R-3 PER THE 2020 FBC SEC. RE 403.5.3. |
| |
| E. THE WATER LINES TO THE SINK IN THE GALLERY FOR THE |
| RECIRCULATING MANIFOLD OF THE HOT WATER LINES SHALL BE |
| SUPPLIED TO THE SOURCE; PLEASE REFER TO THE 2020 FBC |
| ENERGY CODE TABLE C404.5.1. MAXIMUM ALLOWABLE PIPE |
| LENGTH METHOD. |
| |
| F. RECIRCULATING SYSTEM, THE PIPING SHALL BE INSULATED |
| IN ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING |
| OF A CIRCULATING WITH A MIN 1-INCH-THICK PER C404.4 (A) |
| INSULATION OF PIPING. |
| |
| G. ON A GENERAL NOTE, # 3 REFERS TO MIAMI DADE. WOULD |
| YOU PLEASE DELETE PER THE WPB AMENDMENTS TO THE FBC |
| SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| |
| H. WOULD YOU, PLEASE SHOW THE SOURCE LOCATION OF THE |
| WATER SERVICE WITH A FULL OPEN VALVE AND A BACKFLOW |
| DEVICE INTO THE BUILDING AS REQUIRED PER THE 2020 FBC |
| SEC. 606.1 (2) LOCATION OF FULL-OPEN VALVES AND 608.1 |
| GENERAL. |
| |
| 4. ON SHEET P04; |
| |
| A. FOR DETAIL P13, WOULD YOU PLEASE SHOW THE RELIEF |
| LINE DUMPING NOT MORE THAN 6 INCHES ABOVE AND NOT LESS |
| THAN TWO TIMES THE DISCHARGE PIPE DIAMETER ABOVE THE |
| FLOOR OR FLOOD LEVEL RIM OF THE WASTE RECEPTOR OR INTO |
| THE DRAIN PAN SERVING TANK PER THE 2020 FBC SEC P |
| 504.6. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |