Plan Review Notes
Plan Review Notes For Permit 21090393
Permit Number 21090393
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-21 08:09:2410/21/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET A1.0
  
 A. IN THE BREAK ROOM 111 AND THE GALLERY AREA 115 SHOWS
 A SINK, WOULD YOU PLEASE GIVE THE DIMESONS 30 INCHES BY
 48 INCHES PER THE 2020 FBC ACC SEC. 305 CLEAR FLOOR OR
 GROUND SPACE.
  
 B. THERE IS AN ELEVATION OF THE BREAK ROOM 110 A-1, BUT
 THE ELEVATION SHOWS THE COUNTER TO AT THREE FEET INCHES
 MAXIMUM AND IT NEEDS TO BE AT 2 FEET 10 INCHES PER THE
 2020 FBC ACC SEC. 606.3.
  
 C. THE SINK IN THE GALLERY SHOWS A CLEAR FLOOR SPACE
 BUT NO DETAIL FOR THE COUNTER HEIGHT; THIS SHOULD BE AT
 34 INCHES MAXIMUM PER THE 2020 FBC ACC SEC. 606.3.
 WOULD YOU PLEASE PROVIDE DETAIL ON THIS PAGE OR GIVE A
 REFERENCE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THERE IS A SAUNA IN ROOM 110, AND MECHANICAL IS
 REQUESTING MANUFACTURERS SPECIFICATION. PLEASE PROVIDE
 INFORMATION IF IT IS A STEAM UNIT AND NEEDS HOT WATER
 OR A DRAIN PER THE WPB AMENDMENTS TO THE FBC SEC
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
  
 2. ON SHEET P01;
  
 A. IT SHOWS SANITARY ON THE FLOOR. WOULD YOU PLEASE
 SUBMIT A SLAB REPAIR DETAIL FOR REVIEW? SHOW THE WIDTH
 OF THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO
 BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE
 AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH
 INTO THE EXISTING SLAB, AND THE SPACING OF THE DOWELS
 IN THE CENTER. THE REPAIR MAY ALSO INCLUDE TERMITE
 TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER
 OVER THE EARTH. A COPY OF THE TERMITE CERTIFICATE SHALL
 BE ONSITE FOR A FINAL INSPECTION IF APPLICABLE.
  
 B. IT SHOWS A WASHING MACHINE THAT WILL REQUIRE A LINT
 TRAP; PLEASE SUPPLY DETAILS OR NOTES PER THE 2020 FBC
 SEC. 1003.6. A MODEL HLT-1176 IS USED A LOT IN OUR
 MUNICIPALITY, AND YOU ARE WELCOME TO USE THIS ONE OR
 ONE SIMILAR. HTTPS://STRIEMCO.COM/WP-CONTENT/UPLOADS/20
 20/03/6010-6025-001-01-HLT-HLB.PDF .
  
 C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
 3. ON SHEET P02;
  
 A. WOULD YOU PLEASE SHOW THE COLD WATER FOR THE
 RESTROOMS AND THE WATER FOUNTAIN PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. IF COLD WATER EXISTS, PLEASE SHOW AND LABEL
 IT.
  
 B. WOULD YOU PLEASE SHOW THE HAMMER ARRESTORS ON THE
 WASHING MACHINE PER THE 2020 FBC P 604.9.
  
 C. WOULD YOU PLEASE PUT A NOTE NEXT TO THE WATER HEATER
 FOR DETAIL ON SHEET P-4 PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. THERE ARE HOT WATER LINES IN THE GROUND AND NOT IN
 CONDITION SPACE, SO THEY NEED TO BE INSULATED WITH A
 MINIMUM R-3 PER THE 2020 FBC SEC. RE 403.5.3.
  
 E. THE WATER LINES TO THE SINK IN THE GALLERY FOR THE
 RECIRCULATING MANIFOLD OF THE HOT WATER LINES SHALL BE
 SUPPLIED TO THE SOURCE; PLEASE REFER TO THE 2020 FBC
 ENERGY CODE TABLE C404.5.1. MAXIMUM ALLOWABLE PIPE
 LENGTH METHOD.
  
 F. RECIRCULATING SYSTEM, THE PIPING SHALL BE INSULATED
 IN ITS ENTIRETY, INCLUDING THE SUPPLY AND RETURN PIPING
 OF A CIRCULATING WITH A MIN 1-INCH-THICK PER C404.4 (A)
 INSULATION OF PIPING.
  
 G. ON A GENERAL NOTE, # 3 REFERS TO MIAMI DADE. WOULD
 YOU PLEASE DELETE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 H. WOULD YOU, PLEASE SHOW THE SOURCE LOCATION OF THE
 WATER SERVICE WITH A FULL OPEN VALVE AND A BACKFLOW
 DEVICE INTO THE BUILDING AS REQUIRED PER THE 2020 FBC
 SEC. 606.1 (2) LOCATION OF FULL-OPEN VALVES AND 608.1
 GENERAL.
  
 4. ON SHEET P04;
  
 A. FOR DETAIL P13, WOULD YOU PLEASE SHOW THE RELIEF
 LINE DUMPING NOT MORE THAN 6 INCHES ABOVE AND NOT LESS
 THAN TWO TIMES THE DISCHARGE PIPE DIAMETER ABOVE THE
 FLOOR OR FLOOD LEVEL RIM OF THE WASTE RECEPTOR OR INTO
 THE DRAIN PAN SERVING TANK PER THE 2020 FBC SEC P
 504.6.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR