2021-10-05 11:23:05 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21090311 |
| 10/5/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET F1: DESIGN CRITERIA- PLEASE PROVIDE A LIST OF |
| CURRENT CODES AND STANDARDS USED IN THE DESIGN OF THE |
| FOUNTAIN- SECTION 107.2.1 WPB. |
| |
| 2) F1: PLEASE PROVIDE A NOTE ON THE PLAN INDICATING |
| THAT THE FOUNTAIN IS NOT FOR BATHING, SWIMMING, WADING |
| OR FOR INTERACTIVE WATER ACTIVITIES- SECTION 454.1 FBC |
| B. |
| |
| 3) F7.3: PLEASE CORRECT THE DETAIL SHOWING POOL WASTE |
| BY GENERAL CONTRACTOR. THE ENGINEER OF RECORD SHALL |
| DESIGN THE WASTE WATER REMOVAL SYSTEM IN ACCORDANCE |
| WITH- SECTION 454.1.6.5.15 FBC B, AND SECS. 90-126 & |
| 203 WPB CODE OF ORDINANCES. UNDER SEC. 90-126 (5) |
| SWIMMING POOL DISCHARGES ARE PROHIBITED TO DRAIN INTO |
| THE CITY SANITARY SYSTEM. UNDER SEC. 90-203 NO PERSON |
| SHALL DIRECTLY OR INDIRECTLY DISCHARGE, SPILL, OR DUMP |
| INTO ANY OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE |
| STORM SEWER SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER |
| THAN THAT COMPOSED OF STORMWATER. THERE IS AN EXCEPTION |
| UNDER SEC. 90-205 FOR DECHLORINATED SWIMMING POOL |
| DISCHARGES, HOWEVER THE ENGINEER MUST PROVIDE DETAILS |
| AND SPECIFICATIONS FOR DECHLORINATION OF THE POOL WASTE |
| WATER. |
| |
| 4) BASED ON COMMENT #2 ABOVE PLEASE PROVIDE A CIVIL |
| PLAN OR SITE UTILITY PLAN SHOWING HOW WASTE WATER FROM |
| THE POOL AND SPA WILL BE DRAINED TO AN APPROVED PLACE |
| OF DISPOSAL- SECTION 107.2.1 WPB. |
| |
| 5) F7.3: PROVIDE TOTAL DYNAMIC HEAD CALCULATIONS TO |
| VERIFY PUMP SIZING AND PUMP SELECTION SHOWN IN THE PUMP |
| CURVE- SECTION 454.1.6.5.4 FBC B. THE CALCULATIONS |
| SHALL INCLUDE THE CALCULATED HEAD FOR PIPING AND |
| EQUIPMENT. |
| |
| 6) F7.3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE |
| PUMPS, FILTERS, CHLORINATOR AND MAIN DRAINS AND COVERS- |
| SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |