Plan Review Notes
Plan Review Notes For Permit 21090311
Permit Number 21090311
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-05 11:23:051ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21090311
 10/5/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET F1: DESIGN CRITERIA- PLEASE PROVIDE A LIST OF
 CURRENT CODES AND STANDARDS USED IN THE DESIGN OF THE
 FOUNTAIN- SECTION 107.2.1 WPB.
  
 2) F1: PLEASE PROVIDE A NOTE ON THE PLAN INDICATING
 THAT THE FOUNTAIN IS NOT FOR BATHING, SWIMMING, WADING
 OR FOR INTERACTIVE WATER ACTIVITIES- SECTION 454.1 FBC
 B.
  
 3) F7.3: PLEASE CORRECT THE DETAIL SHOWING POOL WASTE
 BY GENERAL CONTRACTOR. THE ENGINEER OF RECORD SHALL
 DESIGN THE WASTE WATER REMOVAL SYSTEM IN ACCORDANCE
 WITH- SECTION 454.1.6.5.15 FBC B, AND SECS. 90-126 &
 203 WPB CODE OF ORDINANCES. UNDER SEC. 90-126 (5)
 SWIMMING POOL DISCHARGES ARE PROHIBITED TO DRAIN INTO
 THE CITY SANITARY SYSTEM. UNDER SEC. 90-203 NO PERSON
 SHALL DIRECTLY OR INDIRECTLY DISCHARGE, SPILL, OR DUMP
 INTO ANY OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE
 STORM SEWER SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER
 THAN THAT COMPOSED OF STORMWATER. THERE IS AN EXCEPTION
 UNDER SEC. 90-205 FOR DECHLORINATED SWIMMING POOL
 DISCHARGES, HOWEVER THE ENGINEER MUST PROVIDE DETAILS
 AND SPECIFICATIONS FOR DECHLORINATION OF THE POOL WASTE
 WATER.
  
 4) BASED ON COMMENT #2 ABOVE PLEASE PROVIDE A CIVIL
 PLAN OR SITE UTILITY PLAN SHOWING HOW WASTE WATER FROM
 THE POOL AND SPA WILL BE DRAINED TO AN APPROVED PLACE
 OF DISPOSAL- SECTION 107.2.1 WPB.
  
 5) F7.3: PROVIDE TOTAL DYNAMIC HEAD CALCULATIONS TO
 VERIFY PUMP SIZING AND PUMP SELECTION SHOWN IN THE PUMP
 CURVE- SECTION 454.1.6.5.4 FBC B. THE CALCULATIONS
 SHALL INCLUDE THE CALCULATED HEAD FOR PIPING AND
 EQUIPMENT.
  
 6) F7.3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE
 PUMPS, FILTERS, CHLORINATOR AND MAIN DRAINS AND COVERS-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  