Plan Review Notes
Plan Review Notes For Permit 21090226
Permit Number 21090226
Review Stop B
Sequence Number 1
Notes
Date Text
2021-10-20 13:18:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21090226
 ADD: 5300 EAST AVENUE ROOMS 118, 119, 120 & 121.
 CONT: FISHER CONTRACTING
 TEL: 561-691-4716
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 20TH/ 2021
 ACTION: DENIED
  
 1) PLEASE NOTE SHEET A-2 PROVIDES THE WIND DESIGN
 CRITERIA BUT NOT THE PRESSURES, PLEASE PROVIDE IN VASD.
 2020 FBC-B 1603.1.4 WIND DESIGN DATA. DESIGN WIND
 PRESSURES TO BE USED FOR EXTERIOR COMPONENTS AND
 CLADDING MATERIALS SPECIFICALLY DESIGNED BY THE
 REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR THE
 DESIGN OF THE STRUCTURE, PSF.
  
 2) IN THE DOCUMENT FOLDER THERE IS A 48-PAGE DOCUMENT
 OF PRODUCT APPROVALS WINDOWS AND DOORS. THE SUB-SYSTEM
 IS IDENTIFIED BUT NOTHING ELSE. IDENTIFY GLAZING/
 MULLIONS. PLEASE IDENTIFY IN THE PRODUCT APPROVAL
 BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE
 SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS
 WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH &
 HEIGHT, SILL HEIGTH, TYPE OF GLAZING, MULLION SIZE,
 LENGTH IF UNREINFORCED OR REINFORCED INFORMATION IF
 REQUIRED, ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH
 OPENING SIZE. 2020 FBC-B 1405.13.1 INSTALLATION.
 WINDOWS AND DOORS SHALL BE INSTALLED IN ACCORDANCE WITH
 APPROVED MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND
 SPACING SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND
 SHALL BE CALCULATED BASED ON MAXIMUM LOADS AND SPACING
 USED IN THE TESTS.
  
 3) SHEET A-5 REFERENCED BATHROOM DETAILS. THE SHEET IS
 MISSING ALL OF THE DETAILS FOR AN ACCESSIBLE SHOWER.
 SEE IN THE 2020 ACCESSIBILITY CODE SECTIONS 608, 609 &
 610 PLEASE PROVIDE DETAILS FOR ACCESSIBILITY.
  
 4) 2020 FBC-ACCESSIBILITY CODE SECTION 467.2.3.21.3.
 ALL SHOWERS IN BATHING ROOMS CONNECTED DIRECTLY TO THE
 RESIDENT ROOMS SHALL BE DESIGNED SO THAT A SHOWER CHAIR
 CAN BE EASILY ROLLED IN AND OUT OF THE SHOWER AREA.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  