Plan Review Notes
Plan Review Notes For Permit 21090225
Permit Number 21090225
Review Stop P
Sequence Number 1
Notes
Date Text
2021-10-29 12:56:1910/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW,
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET G-0, THERE IS A LIST OF DRAWINGS MISSING;
 L-S1, A3-103, AND S, M, E, P ARE NOT LISTED. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 2. ON SHEET G-1;
  
 A. UNDER CODES STANDARDS, THERE IS NO SAFE HARBOR
 MENTIONED FOR FHA. ARE YOU USING THE DESIGN MANUAL OR
 THE GUIDELINES? WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE PROVIDE THE EDITION USED IN THE
 2020 CODES MENTIONED PER THE WPB AMENDMENTS TO FBC
 102.3 APPLICATION OF REFERENCES.
  
 3. ON SHEET G-2;
  
 A. UNDER GOVERNING CODES, THERE IS NO SAFE HARBOR
 MENTIONED FOR FHA. ARE YOU USING THE DESIGN MANUAL OR
 THE GUIDELINES? WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE PROVIDE THE EDITION USED IN THE
 GOVERNING CODES MENTIONED PER THE WPB AMENDMENTS TO FBC
 102.3 APPLICATION OF REFERENCES.
  
 4. ON SHEET LS-01;
  
 A. WOULD YOU PLEASE PROVIDE THE TABLE USED AND THE
 NUMBER OF OCCUPANTS IN THE PLUMBING FIXTURE COUNT FOR
 THE LOBBY, RETAIL AREA, AND COMMERCIAL SPACE PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 5. ON SHEET A1-1.02;
  
 A. WOULD YOU PLEASE LABEL THE UNIT TYPE THAT ARE FHA,
 EITHER A OR B WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. ON SHEET A1-1.03;
  
 A. WOULD YOU PLEASE PROVIDE THE TABLE USED FOR THE
 STORMWATER PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE CORRECT THE SCUPPER DETAIL NOTE; IT
 SAYS A6 BUT IS A7-107 DETAIL 10.
  
 C. WOULD YOU PLEASE PROVIDE THE SQUARE FOOTAGE BEING
 DRAINED TO DETERMINE THE GPM AND SHOW THE SIZE OF THE
 ROOF DRAIN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. ON SHEET A1-201;
  
 A. PLAN NOTES SAY REFER TO SHEET A0-0.00 AND NO SUCH
 PAGE. WOULD YOU PLEASE PROVIDE THE CORRECT PAGE NUMBER
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? THIS IS A
 TYPICAL COMMENT FOR OTHER PAGES
  
 B. GENERAL NOTES REFERS TO THE CITY OF MIAMI BEACH.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 8. ON SHEET A1-301, 302, AND 303;
  
 A. PLAN NOTES SAY REFER TO SHEET A0-0.00 AND NO SUCH
 PAGE. WOULD YOU PLEASE PROVIDE THE CORRECT PAGE NUMBER
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. GENERAL NOTES REFERS TO THE CITY OF MIAMI BEACH.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. WOULD YOU PLEASE LABEL THE UNIT TYPE THAT ARE FHA,
 EITHER A OR B WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 FHA ON THE SINK, IN FRONT OF THE REFRIGERATOR, TUB,
 LAV, AND TOILET. WOULD YOU PLEASE SHOW PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 9. ON SHEET A4-102;
  
 A. THE ELEVATOR SHOWS A PIT, AND IN THE PIT, WILL THERE
 BE A PUMP TO PUMP OUT WATER? IF SO, WOULD YOU PLEASE
 PROVIDE DETAIL THAT HAS A PUMP DETAIL AND SHOW AN
 INDIRECT WASTE ON FLAT AND ISOMETRIC DRAWINGS? WOULD
 YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 10. ON SHEET A4.103;
  
 A. IN SOME APPLICATIONS OF A TRASH SHOOT, THERE IS A
 SANITIZING DISPENSER ON THE TOP FLOOR. IF ONE WILL BE
 PROVIDED WOULD YOU, PLEASE SHOW A DETAIL ALONG WITH
 SHUTOFF AND AN ATMOSPHERIC VACUUM BREAKER THAT COMPLIES
 WITH THE 2020 FBC P 608.14.6ATMOSPHERIC-TYPE VACUUM
 BREAKERS.
  
 B. IT MOTIONS A HOSE BIBB IN THE GENERAL NOTES. WOULD
 YOU PLEASE SHOW THE ISOMETRIC AND THE LOCATION AND GIVE
 THE DETAILED SECTION SHEET PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 11. ON SHEET A1-501;
  
 A. WOULD YOU PLEASE LABEL THE UNIT TYPE THAT ARE FHA,
 EITHER A OR B PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 FHA ON THE SINK, IN FRONT OF THE REFRIGERATOR, TUB,
 LAV, AND TOILET PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 E. THE FAIR HOUSING ACT PROVIDES TWO SETS OF
 SPECIFICATIONS TO DESIGN BATHROOMS THAT ARE USABLE BY
 PEOPLE WITH DISABILITIES. THOUGH THERE ARE OTHER
 DIFFERENCES, SPECIFICATION B BATHROOMS OFFER GREATER
 ACCESS TO THE TUB THAN SPECIFICATION A BATHROOMS.
  
 IF THE SPECIFICATION A DESIGN IS SELECTED, ALL
 BATHROOMS IN THE UNIT MUST COMPLY WITH THE
 SPECIFICATION A STANDARD (SECTION 7.14). THIS INCLUDES
 ACCESS TO ALL FIXTURES IN EACH SPECIFICATION A BATHROOM
 (E.G., TWO LAVATORIES IN ONE BATHROOM WOULD BOTH NEED
 TO MEET FHA REGULATIONS).
  
 IF THE SPECIFICATION B DESIGN IS SELECTED, ONLY ONE
 BATHROOM IN THE UNIT, AND ONLY ONE OF EACH TYPE OF
 FIXTURE WITHIN THE BATHROOM, MUST COMPLY WITH
 SPECIFICATION B STANDARDS (SECTION 7.15). ALL OTHER
 BATHROOMS IN THE UNIT MUST MEET THE USABLE BATHROOM
 REQUIREMENTS (SECTION 7.11), EXEMPTING MANEUVERING
 CLEARANCES, AND CLEAR FLOOR SPACE REQUIREMENTS AT
 FIXTURES. THE TOP FIXTURE RIM IS A MAXIMUM OF 34 INCHES
 AFF, WITH THE APRON AT LEAST 27 INCHES AFF. IN
 INSTANCES WHERE REMOVABLE CABINETRY IS PROVIDED, PIPES
 ARE COVERED FOR PROTECTION; INSULATION AROUND PIPES, OR
 ADDING A FIXED, ONE-PIECE PROTECTION PANEL.
  
 F. FOR ALL BATHROOM DIMENSIONS OF THE FIXTURES SHALL
 COMPLY WITH THE 2020 FBC SEC. P 405.3.1 WATER CLOSETS
 AND LAVATORIES. THE FHA HAS SOME DIMENSIONS THAT MAY BE
 DIFFERENT. SHOW THE DEPTH OF THE NEW VANITY. THE VANITY
 SHALL BE A MAXIMUM OF 24 INCHES DEEP PER THE FAIR
 HOUSING ACT. ADDITIONAL REINFORCEMENT MAY BE REQUIRED
 IN THE WALLS AROUND THE TUB TO ALLOW FOR THE FUTURE
 INSTALLATION OF GRAB BARS PER THE FAIR HOUSING ACT.
  
 G. SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE TUB OR
 SHOWER IN ACCORDANCE WITH THE FAIR HOUSING ACT.
  
 12. ON SHEET A5-1.02;
  
 A. UNDER NOTE, IT REFERS TO THE FBC 2014 R 307.2, WHICH
 IS THE WRONG CODE YEAR, AND OTHER COMMENTS ABOUT THE
 SHOWER THAT HAS NOTHING TO DO WITH THIS DRAWING. WOULD
 YOU PLEASE REMOVE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. UNDER INTERIOR FISHES, THERE ARE SHOWER GLASS
 COMMENTS THAT DON'T PERTAIN TO THIS DRAWING. WOULD YOU
 PLEASE REMOVE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. THESE RESTROOMS ARE TO COMPLY WITH THE 2020 FBC
 ACCESSIBILITY CODE. PLEASE PROVIDE THIS INFORMATION ON
 THIS PAGE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 D. WOULD YOU PLEASE GIVE DIMENSIONS FOR FIXTURE
 CLEARANCES PER FLORIDA BUILDING CODE AND FLORIDA
 ACCESSIBILITY CODE FOR TOILET AND LAV.
  
 E. PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE LAVATORY PER THE 2020 FBC ACC SEC.
 606.2 CLEAR FLOOR SPACE. THE LAV NEEDS TO SHOW THE
 DIMENSIONS OF THE CLEAR FLOOR SPACE OF 30? X 48? PER
 THE 2020 FBC SEC. ACC 305.3.
  
 F. THE BOTTOM ON THE LAV SHALL BE A MINIMUM OF 27" KNEE
 CLEARANCE PER THE 2020 FBC SEC. 306.3.
  
 G. WOULD YOU PLEASE SHOW THE WATER CLOSET FLUSH CONTROL
 LOCATION PER THE 2020 FBC SEC. 604.6 FLUSH CONTROLS.
  
 H. WOULD YOU PLEASE SHOW THE FLUSH CONTROLS SHALL BE
 LOCATED ON THE OPEN SIDE OF THE WATER CLOSET PER THE
 2020 ACC SEC. 604.6 FLUSH CONTROLS.
  
 J. THE WATER CLOSET IN THE ACCESSIBLE RESTROOM SHALL BE
 TO THE CENTERLINE OF THE WATER CLOSET 16 INCHES MINIMUM
 TO 18 INCHES MAXIMUM FROM THE SIDE WALL PER THE 2020
 FBC ACC. SEC. 604.2 LOCATION.
  
 K. THE GRAB BARS ARE NOT SHOWN. WOULD YOU PLEASE SHOW
 THEM MEASURED TO THE TOP OF THE GRIPPING SURFACE PER
 THE 2020 FBC ACC SEC. 609.4.
  
 L. WOULD YOU PLEASE SHOW THE GRAB BARS, WHICH SHALL BE
 INSTALLED IN A HORIZONTAL POSITION PER THE 2020 FBC ACC
 SEC. 609.4.
  
 L. WOULD YOU PLEASE SHOW THE HORIZONTAL GRAB BARS WHICH
 NEED TO BE MEASURED TO THE CENTER OF THE BAR PER THE
 2020 FBC ACC SEC. 604.5.1 SIDE WALL AND 604.5.2 REAR
 WALL.
  
 M. WOULD YOU PLEASE SHOW THE HORIZONTAL GRAB BARS ON
 THE REAR TO BE MEASURED TO THE CENTER OF THE WATER
 CLOSET TO 12 INCHES TO THE WALL AND 24 INCHES TO THE
 OPEN SIDE PER THE 604.5.1 SIDE WALL AND 604.5.2 REAR
 WALL.
  
 N. WOULD YOU PLEASE PROVIDE CABINET DETAIL SHOWING THE
 SINK AND OR LAVS HEIGHT OF 34 INCHES MAXIMUM PER THE
 2020 FBC ACC SEC. 606.3.
  
 O. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDEWALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1.
  
 P. THE DOORS ARE SWINGING IN THE CLEAR FLOOR SPACE OF
 THE LAVS. WOULD YOU PLEASE SHOW THE TURNING SPACE
 DIAMETER- SPACE OF 60 INCHES DIAMETER MINIMUM AND
 INSIDE OF THAT THE 30 INCHES BY 60 INCHES PER THE 2020
 FBC ACC SEC. 304.3. YOU CAN ALSO HAVE THE DOOR SWING
 OUT AND NOT SHOW THIS.
  
 Q. WOULD YOU PLEASE SHOW THE TOILET PAPER DISPENSERS
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 DISPENSER PER THE 2020 FBC ACC SEC. 604.7.
  
 R. WOULD YOU PLEASE PROVIDE A NOTE OR SHOW THE LAVATORY
 WATER SUPPLY AND DRAINPIPES UNDERSIDE THAT SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 S. WOULD YOU PLEASE SHOW THE TOILET SEAT TO BE 17
 INCHES TO 19 INCHES MAXIMUM MEASURED TO THE TOP OF THE
 SEAT PER THE 2020 FBC ACC SEC. 604.4 SEATS.
  
 T. WOULD YOU PLEASE SHOW THE REFLECTIVE PART OF THE
 MIRROR NEEDS TO BE THE 40" TO THE REFLECTIVE SIDE PER
 THE 2020 FBC ACC SEC. 603.3.
  
 U. WOULD YOU PLEASE PROVIDE A NOTE THAT THE SEATS OF
 WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER 2020 FBC P
 425.3 WATER CLOSET SEATS
  
 13. ON SHEET A5-103;
  
 A. DETAIL ONE SHOWS A U SHAPE, AND A 60-INCH TURNING
 CIRCLE IS REQUIRED. WOULD YOU PLEASE AND PER THE FHA
 PAGE 7.9.
  
 14. ON SHEET A5-104;
  
 A. THE DETAIL FOR THE GRAB BARS IS NOT REQUIRED AS THEY
 DO NOT NEED TO BE INSTALLED FOR COMPLIES, AND ONLY THE
 BACKING NEEDS TO BE SHOWN. WOULD YOU PLEASE DELETE TO
 PREVENT FIELD CONFUSION PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE SHOW THE WATER CLOSET DIMENSIONS
 THAT COMPLY WITH THE DESIGNED BATHROOMS AS PER PAGE
 7.43 OF THE FHA DESIGN MANUAL.
  
 C. WOULD YOU PLEASE SHOW THE HEIGHT OF THE LAV IN THE
 SPECIFICATION TYPE "B" WILL BE THE USE OF 34 INCHES IN
 THE BATHROOMS AS PER FHA DESIGN MANUAL PAGE 7.52.
  
 15. ON SHEET A7-1.09;
  
 A. THE FIRE PENETRATIONS FOR CAJ 2392, WL 12, AND WL
 2128 FROM HILTI HAVE VERY LIGHT VERBIAGE. WOULD YOU
 PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 16. ON SHEET P-1.0;
  
 A. WOULD YOU PLEASE SHOW THE ADA FIXTURES SCHEDULE FOR
 THE ACCESSIBLE RESTROOM PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. UNDER PLUMBING FIXTURES FOR COMMENT ONE, IT REFERS
 TO MIAMI DADE COUNTY AMENDMENTS. WE HAVE OUR
 AMENDMENTS, AND A COPY CAN BE FURNISHED BY CONTACTING
 ME IF YOU LIKE. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. IN THOSE SAME COMMENTS, TWO AND THREE ARE NOT THE
 CORRECT CODE REFERENCES, AND WOULD YOU PLEASE GIVE THE
 WHOLE YEAR AND EDTION YOU REFER TO PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION? ON
 CONSTRUCTION DOCUMENTS.
  
 D. UNDER PLUMBING GENERAL NOTES, NUMBER 16 REFERS TO
 STACKS WITH A CLEANOUT AT THE BASE OF STACK OR VENT AND
 IN THE NEW CODE CYCLE THAT WAS ELIMINATED. THAT MAY BE
 AN RFI IN THE FIELD. THE INSPECTOR MAY ASK TO BE
 INSTALLED IN DRAWING, WHICH MOST PLUMBING CONTRACTORS
 DO NOT DO ANYMORE. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 E. ON THOSE SAME NOTES FOR NUMBER 19, IT SAYS
 UNDERGROUND PIPING TO BE HUNG FROM THE SLAB. YOU MAY
 KEEP THAT BUT NOT REQUIRED BY OUR CODE. IF SO, WOULD
 YOU PROVIDE DETAIL ON HOW DISTANCE AND MATERIALS ARE
 BEING USED PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 F. ON NUMBER 23, THE ANTI-SCALDING THE 110, I PRESUME,
 IS THE TEMPERATURE WHICH IN THE CODE IS 120 PER THE
 2020 FBC SEC. P 412.3INDIVIDUAL SHOWER VALVES. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 G. WOULD YOU PLEASE PROVIDE DETAIL FOR THE TANKLESS AND
 SPECIFICATIONS IN THE UNITS AND THE COMMERCIAL PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 17. ON SHEET P-2.0;
  
 A. THE WATER ISOMETRIC SHOWS THE WATER FOR BOTH IN ONE
 SERVICE LINE FOR HOT WATER AND THE COLD PER THE 2020
 FBC SEC. P 606.1 (6) LOCATION OF FULL-OPEN VALVES.
 WOULD YOU SEPARATE THEM AS THEY ARE INDIVIDUAL UNITS,
 AND BUILD-OUT MAY CAUSE ISSUES IN THE FUTURE? PLEASE
 SHOW ITS OWN WATER SERVICE AND HOT TANKLESS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. WOULD YOU PLEASE SHOW SHUT-OFF VALVES FOR ALL RISERS
 WITH ACCESS PANELS IN THE GARAGE AREA PER THE 2020 FBC
 SEC? P 606.1 (4) LOCATION OF FULL-OPEN VALVES.
  
 C. WOULD YOU PLEASE SHOW ON THE ISOMETRIC A TRAP PRIMER
 AND ITS SOURCE PER THE 2020 FBC SEC. 1002.4.1 TRAP SEAL
 PROTECTION.
  
 D. WOULD YOU PLEASE SHOW THE CLEANOUT ON THE BUILDING
 DRAIN PER THE 2020 FBC SEC. P 708.1.3BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
  
 E. WOULD YOU PLEASE SHOW A BACKFLOW DEVICE NEXT TO THE
 METER AND PUT A SEPARATE PERMIT REQUIRED FOR THE
 BACKFLOW DEVICE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 18. ON SHEET P-2.2;
  
 A. CORRECTION NEEDS TO BE MADE TO THE PLUMBING LAYOUT.
 PLEASE REFER TO COMMENT 20 TO MATCH SANITARY RISER PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 B. WASHING MACHINE VALES SHALL BE ACCESSIBLE WITHOUT
 MOVING THE UNIT PER THE 2020 FBC SEC. P 606.3.
 ACCESSIBLE SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL
 OF AN ACCESS PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
  
 19. ON SHEET P-3.0;
  
 A. IN THE GENERAL SANITARY RISER, WOULD YOU PLEASE SHOW
 A CLEANOUT ON EACH ENTRANCE TO THE BUILDING (COMMERCIAL
 SPACE AND UNITS). THE FOUR-INCH CLEAN-OUT-UP MAY NEED
 TO BE MOVED BEFORE THE WYE AND ADD ONE DOWNSTREAM OF
 THE WYE PER THE 2020 FBC SEC. 708.1.3BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
  
 B. IN THE GENERAL WATER RISER, THERE IS ONE METER, BUT
 IT GOES UP AND FEEDS TWO UNITS SHOULD THEY BE IN THE
 UNITS AND BE TWO INSTEAD OF ONE. WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN THAT SAME RIDER, THE COLD LINE TO THE COMMERCIAL
 SPACE IS MISSING A DIMENSION BEFORE IT TEES OFF FROM
 THE 1 1/4 LINE. WOULD YOU PLEASE ADD THE SIZE PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. THERE IS NO ISOMETRIC FOR THE CONDENSATE LINES WITH
 A P-TRAP AND UNDER 2020 FBC M307.2.4 AND P1002.1. EACH
 TRAP SHALL BE VENTED TO PERMIT THE ADMISSION OR
 EMISSION OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP
 SHALL NOT BE SUBJECTED TO A PRESSURE DIFFERENTIAL OF
 MORE THAN 1 INCH OF WATER COLUMN PER THE 2020 FBC
 SECTION 901.2 TRAP SEAL PROTECTION. THE CONDENSATE LINE
 SHOULD SHOW A VENT TERMINATION AND LOCATION, AND THEY
 CANNOT TERMINATE IN A WALL AS IT HAS NO NEGATIVE OR
 POSITIVE PRESSURE TO HAVE A DIFFERENTIAL OF ONE-INCH
 WATER COLUMN. WOULD YOU PLEASE PROVIDE DETAIL OF HOW
 THEY WILL BE VENTED PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. IF
 TERMINATION IN PLENUM, IT MUST BE CPVC THAT HAS THE
 REQUIRED SMOKE INDEX.
  
 E. CONDENSATE IS NOT PERMITTED TO DISCHARGE INTO THE
 CITY'S SANITARY SYSTEM PER CITY ORDINANCE CHAPTER 90,
 ARTICLE III, SEC.90-126 (B)(5). THEY SHALL DISPOSE OF
 IN A SAFE LOCATION OR A DRY WELL. IF A DRY WELL WILL BE
 USED, WOULD YOU PLEASE PROVIDE DETAILS OF THE DRY WELL
 FOR THE CONDENSATE LINE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 E. WOULD YOU PLEASE SHOW STORM LINES ON THE LAYOUT AND
 ISOMETRIC WITH ITS SIZE AND LOCATION OF TERMINATION PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 F. HOSE BIBB NOT SHOWN FOR THE TRASH SHOOT, AND IF ANY
 OTHER HOSE BIBB IS REQUIRED FOR THE COMMON AREAS, WOULD
 YOU PLEASE SHOW A SHUT-OFF VALVE PER THE 2020 FBC SEC.
 P 606.2 (2) LOCATION OF SHUTOFF VALVES.
  
 20. ON SHEET P-3.01;
  
 A. ON ALL SANITARY RISERS, THE FIXTURE DRAIN FOR THE
 STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER SHALL
 CONNECT TO A 3-INCH OR LARGER DIAMETER FIXTURE BRANCH
 OR STACK PER THE 2020 FBC SEC. R 406.2 WASTE
 CONNECTION.
  
 B. IN THE SAME RISERS, BATHROOM GROUPS ( D, C AND E)
 HAVE THE TOILET AND THE SHOWER NOT VENTED. THE VENT
 NEEDS TO GO BETWEEN THE TOILET AND THE SHOWER OR USE A
 DOUBLE WYE PATTERN AS EACH TRAP SHALL BE VENTED PER THE
 2020 FBC SEC. 910.1 INDIVIDUAL VENTS PERMITTED.
  
 C. THE ISOMETRIC DOES NOT SHOW VALVES TO SHUT OFF EACH
 UNIT IN SOME UNIT TYPE WITH THE CONNECTION IS UNCLEAR.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  