2021-10-26 16:42:50 | NEW 3 STORY BUILDING |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE 2ND FLOOR, |
| 3RD FLOOR AND ROOF TERRACE - SHOW THE OCCUPANCY LOADS, |
| EXIT ACCESS TRAVEL DISTANCE TO THE EXIT DISCHARGE ETC. |
| FBC WPB 107.3.5.1.1 (6) |
| |
| 2) DRAWING LS-01 SHOWS BUILDING CONSTRUCTION TYPE (I) - |
| PLEASE SHOW (IA OR IB) FBC CHAPTER 6 |
| |
| 3) DRAWING LS-01 DOES NOT SHOW THE OCCUPANCY FOR EACH |
| ROOM - PLEASE SHOW THE OCCUPANT LOAD FOR EACH ROOM OR |
| SPACE - FBC 1004.1.2 |
| |
| 4) 2 EXITS ARE REQUIRED FROM EACH STORY AND ROOF |
| TERRACE FBC 1006.3 |
| |
| 5) THE TRASH CHUTE CANNOT OPEN TO A CORRIDOR - FBC |
| 713.13.1 - FBC 713.13.3 CHUTE ACCESS ROOMS. |
| ACCESS OPENINGS FOR WASTE OR LINEN CHUTES SHALL BE |
| LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS |
| THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| IN ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO |
| THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING |
| PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS |
| THAN 3/4 HOUR. DOORS SHALL BE SELF- OR |
| AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN |
| ACCORDANCE WITH SECTION 716.5.9.3. |
| |
| 6) PLEASE SHOW THE STAIR RISER HEIGHTS FBC 1011.5.2 |
| |
| 7) DRAWING A4-1.01 PLEASE SHOW THE BOTTOM HAND RAIL |
| EXTENSION TO CONTINUE TO SLOPE (NOT LEVEL) - FBC 1014.6 |
| |
| 8) PLEASE PROVIDE THE EXTERIOR FRAMING DETAILS FBC WPB |
| 107.2.1 |
| |
| 9) PLEASE PROVIDE THE EXTERIOR CLADDING (TEAK WOOD |
| FINISH) DETAILS FBC WPB 107.2.1 |
| |
| 10) PLEASE SHOW THE HORIZONTAL ASSEMBLY HOURLY FIRE |
| RATING TO COMPLY WITH FBC 711.2.4 |
| |
| 11) PLEASE SHOW THE ROOFING SYSTEM REQUIRED WIND DESIGN |
| PRESSURES FBC 1603.1.4 |
| |
| 12) PLEASE SHOW THE GUARDRAIL HEIGHT FROM THE ROOF |
| TERRACE FINISHED FLOOR TO THE TOP OF THE PARAPET (GUARD |
| RAIL). FBC 1015.3 |
| |
| 13) PLEASE PROVIDE A SURVEY. |
| |
| 14) PLEASE SHOW THE COMMERCIAL RESTROOMS WALL FINISH - |
| FBC 1210.2.2 WALLS AND PARTITIONS. |
| WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| CONSIDERED A HARD SURFACE) |
| |
| 15) PLEASE PROVIDE COPIES OF ALL OF THE PRODUCT |
| APPROVALS (NOA) MENTIONED ON THE DRAWINGS. |
| |
| 16) PROVIDED NOA 20-0813.03 FOR THE SLIDING WINDOWS |
| REQUIRES SHUTTERS - PLEASE PROVIDE THE SHUTTER PRODUCT |
| APPROVALS. PRODUCT APPROVALS THAT ARE NOT LISTED ON THE |
| DRAWINGS NEED TO BE REVIEWED AND MARKED APPROVED BY THE |
| DESIGNER OF RECORD FBC WPB 107.3.4 |
| |
| 17) DRAWING A1-1.01 SHOWS DOOR OR SOMETHING AS SF-2 - |
| WHAT IS SF-2 ? |
| |
| 18) PLEASE SHOW THE COMMERCIAL RESTROOMS TO COMPLY WITH |
| FBC ACCESSIBILITY - SHOW FIXTURE FLOOR SPACES, GRAB BAR |
| LOCATION AND SIZE DIMENSIONS, TOILET PAPER HOLDER |
| LOCATION DIMENSIONS, MIRROR LOCATION DIMENSIONS PER FBC |
| ACCESSIBILITY CHAPTER 6. |
| |
| 19) PLEASE SHOW RESIDENTIAL UNIT COMPLIANCE WITH FHA - |
| SHOW THE REQUIRED FLOOR SPACE IN THE UNITS - - |
| REQUIREMENT 7 -USABLE KITCHENS AND BATHROOMS. |
| SECTION 100.205(C)(3)(IV) REQUIRES THAT COVERED |
| MULTIFAMILY DWELLINGS WITH A BUILDING ENTRANCE ON AN |
| ACCESSIBLE ROUTE SHALL BE DESIGNED AND CONSTRUCTED IN |
| SUCH A MANNER THAT ALL PREMISES WITHIN COVERED |
| MULTIFAMILY DWELLING UNITS CONTAIN USABLE KITCHENS AND |
| BATHROOMS SUCH THAT AN INDIVIDUAL IN A WHEELCHAIR CAN |
| MANEUVER ABOUT THE SPACE. |
| GUIDELINE(1)USABLE KITCHENS. USABLE KITCHENS WOULD MEET |
| SECTION 100.205(C)(3)(IV) IF: |
| (A)A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| THAT ALLOWS A PARALLEL APPROACH BY A PERSON IN A |
| WHEELCHAIR IS PROVIDED AT THE RANGE OR COOKTOP AND SINK |
| AND EITHER A PARALLEL OR FORWARD APPROACH IS PROVIDED |
| AT OVEN, DISH WASHER, REFRIGERATOR/FREEZER OR TRASH |
| COMPACTOR. (SEE FIGURE FHAG-6) |
| (B)CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE |
| CABINETS, COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST |
| 40 INCHES. |
| (C)IN U-SHAPED KITCHENS WITH SINK OR RANGE OR COOKTOP |
| AT THE BASE OF THE ?U?, A 60-INCH TURNING RADIUS IS |
| PROVIDED TO ALLOW PARALLEL APPROACH, OR BASE CABINETS |
| ARE REMOVABLE AT THAT LOCATION TO ALLOW KNEE SPACE FOR |
| A FORWARD APPROACH. |
| |
| (2)USABLE BATHROOMS. TO MEET THE REQUIREMENTS OF |
| SECTION 100.205(C)(3)(IV) EITHER. |
| ALL BATHROOMS IN THE DWELLING UNIT COMPLY WITH OPTION |
| 2, OR THE PROVISIONS OF PARAGRAPH (A): OR |
| AT LEAST ONE BATHROOM IN THE DWELLING UNIT COMPLIES |
| WITH THE PROVISIONS OF PARAGRAPH (B), AND ALL OTHER |
| BATHROOMS AND POWDER ROOMS WITHIN THE DWELLING UNIT |
| MUST BE ON AN ACCESSIBLE ROUTE WITH USABLE ENTRY DOORS |
| IN ACCORDANCE WITH THE GUIDELINES FOR REQUIREMENTS 3 |
| AND 4. |
| |
| 20) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: |
| |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. |
| PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING |
| SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY |
| DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP |
| CEILING DESCRIPTION) |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP |
| CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING |
| ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED |
| DROP CEILING DESCRIPTION) |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS |
| ATTACHED TO THE FLOORING) |
| |
| 21) PLEASE PROVIDE DETAILS SHOWING THAT THE UNIT |
| SEPARATION WALLS COMPLY WITH THE AIRBORNE SOUND |
| REQUIREMENTS FBC 1207.2 AIRBORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN |
| TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE |
| SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND |
| FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY |
| ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND |
| TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST |
| PROCEDURES SET FORTH IN ASTM E90. PENETRATIONS OR |
| OPENINGS IN CONSTRUCTION ASSEMBLIES FOR PIPING; |
| ELECTRICAL DEVICES; RECESSED CABINETS; BATHTUBS; |
| SOFFITS; OR HEATING, VENTILATING OR EXHAUST DUCTS SHALL |
| BE SEALED, LINED, INSULATED OR OTHERWISE TREATED TO |
| MAINTAIN THE REQUIRED RATINGS. THIS REQUIREMENT SHALL |
| NOT APPLY TO ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL |
| BE TIGHT FITTING TO THE FRAME AND SILL. |
| |