Plan Review Notes
Plan Review Notes For Permit 21090218
Permit Number 21090218
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-27 11:54:331ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21090218
 9/27/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P1 & P2: PLEASE PROVIDE THE SPECIFIC
 INSTA-HOT MODEL TO BE INSTALLED FOR THE HOT WATER
 SUPPLY TO THE BREAKROOM SINK AND DISHWASHER. PLEASE
 NOTE THAT HOT WATER IS REQUIRED TO THE FIXTURES AND
 TEMPERED WATER USING A MIXING VALVE OR INTEGRAL
 TEMPERATURE LIMITING DEVICE IN THE WATER HEATER IS NOT
 ALLOWED- SECTION 607.1 WPB.
  
 2) P1: PROVIDE WATER HAMMER ARRESTORS FOR SUPPLY LINES
 TO THE DISHWASHER AND REFRIGERATOR ICE MAKER- SECTION
 604.9, AND A BACKFLOW PREVENTER FOR THE ICEMAKER-
 608.3.
  
 3) PROVIDE AN ENLARGED BREAKROOM FLOOR PLAN SHOWING THE
 CLEAR FLOOR SPACE APPROACH DIAGRAMS AND DIMENSIONS AT
 THE SINK, DISHWASHER AND REFRIGERATOR- SECTIONS 305,
 606.2, 804.6.3 & 804.6.6 FBC ACC. PROVIDE AN ELEVATION
 DETAIL OR NOTE TO VERIFY THE FREEZER INSIDE THE
 REFRIGERATOR HAS A MINIMUM OF 50 PERCENT OF FREEZER
 SPACE 54-INCHES MAXIMUM FROM THE FINISHED FLOOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  