2021-09-27 11:54:33 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21090218 |
| 9/27/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS P1 & P2: PLEASE PROVIDE THE SPECIFIC |
| INSTA-HOT MODEL TO BE INSTALLED FOR THE HOT WATER |
| SUPPLY TO THE BREAKROOM SINK AND DISHWASHER. PLEASE |
| NOTE THAT HOT WATER IS REQUIRED TO THE FIXTURES AND |
| TEMPERED WATER USING A MIXING VALVE OR INTEGRAL |
| TEMPERATURE LIMITING DEVICE IN THE WATER HEATER IS NOT |
| ALLOWED- SECTION 607.1 WPB. |
| |
| 2) P1: PROVIDE WATER HAMMER ARRESTORS FOR SUPPLY LINES |
| TO THE DISHWASHER AND REFRIGERATOR ICE MAKER- SECTION |
| 604.9, AND A BACKFLOW PREVENTER FOR THE ICEMAKER- |
| 608.3. |
| |
| 3) PROVIDE AN ENLARGED BREAKROOM FLOOR PLAN SHOWING THE |
| CLEAR FLOOR SPACE APPROACH DIAGRAMS AND DIMENSIONS AT |
| THE SINK, DISHWASHER AND REFRIGERATOR- SECTIONS 305, |
| 606.2, 804.6.3 & 804.6.6 FBC ACC. PROVIDE AN ELEVATION |
| DETAIL OR NOTE TO VERIFY THE FREEZER INSIDE THE |
| REFRIGERATOR HAS A MINIMUM OF 50 PERCENT OF FREEZER |
| SPACE 54-INCHES MAXIMUM FROM THE FINISHED FLOOR. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |