2021-09-23 12:55:27 | 09/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET P1.1, THE SANITARY LINES ARE SHOWN COMING |
| IN AT DIFFERENT POINTS, WHICH CONSTRUED A NEW SYSTEM AT |
| EACH ENTRY. AS IT ENTERS THE BUILDING, IT IS CONSIDERED |
| A BUILDING DRAIN THAT REQUIRES A VENT THROUGH THE ROOF |
| AND CLEAN-OUT FOR EACH SYSTEM. YOU MAY MINIMIZE THIS BY |
| DOING TWO, ONE ON EACH SIDE. WOULD YOU PLEASE REFER TO |
| THE FOLLOWING 2020 FBC R P3005.2.3 BUILDING DRAIN AND |
| BUILDING SEWER JUNCTION AND R3102.1 REQUIRED VENT |
| EXTENSION, THE VENT SYSTEM SERVING EACH BUILDING DRAIN |
| SHALL HAVE NOT LESS THAN ONE VENT PIPE; THAT EXTENDS TO |
| THE OUTDOORS? |
| |
| 2. ON SHEET P1.2; |
| A. THERE IS A WATER FEATURE IN THE COURTYARD. WOULD YOU |
| PLEASE PROVIDE A DETAIL AND BACKFLOW DEVICE BEING USED |
| UNDER THE PLUMBING FIXTURE CONNECTION SCHEDULE ON PAGE |
| P1.0 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 |
| (12) RESIDENTIAL PLUMBING. |
| |
| B. THERE IS A BACKFLOW DEVICE AT THE METER THAT |
| PROTECTS THE CITY OF WEST PALM BEACH WITH THEIR |
| UTILITIES DEPARTMENT; CROSS CONNECTION PROGRAM MAY NEED |
| TO BE A REDUCED PRINCIPAL VACUUM BREAKER. THE SECOND |
| BACKFLOW IS A PRESSURE VACUUM BREAKER AT THE METER, BUT |
| K COPPER IS NOT ALLOWED ON THE SIDE FROM THE METER TO |
| THE DEVICE, ONLY L COPPER. WOULD YOU PLEASE CONTACT |
| THEM TO DETERMINE WHAT THE NEEDED AT 561-822-2240? |
| |
| C. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW |
| DEVICES PER THE WPB AMENDMENTS TO FBC SEC. 105.1. |
| |
| D. HOT WATER LINES UNDER SLAB NOT IN CONDITION SPACE |
| NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 |
| FBC SEC. RE 403.5.3. PLEASE PLACE A NOTE. |
| |
| E. IF THE TANKLESS HAS A CONDENSATE, IT NEEDS TO BE 1' |
| AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC. R318.5. |
| |
| 3. ON SHEET P1.4; |
| A. ON THE ISOMETRIC FOR THE HOT WATER RECIRCULATING |
| SYSTEM, THERE IS NO CONTINUOUS LOOP ON THE SYSTEM AS IT |
| TEE?S OFF IN SEVERAL LOCATIONS. WOULD YOU PLEASE |
| CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| B. HOT WATER LINES OUTSIDE NOT IN CONDITION SPACE NEED |
| TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC |
| SEC. RE 403.5.3. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |