Plan Review Notes
Plan Review Notes For Permit 21090139
Permit Number 21090139
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-23 12:55:2709/23/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P1.1, THE SANITARY LINES ARE SHOWN COMING
 IN AT DIFFERENT POINTS, WHICH CONSTRUED A NEW SYSTEM AT
 EACH ENTRY. AS IT ENTERS THE BUILDING, IT IS CONSIDERED
 A BUILDING DRAIN THAT REQUIRES A VENT THROUGH THE ROOF
 AND CLEAN-OUT FOR EACH SYSTEM. YOU MAY MINIMIZE THIS BY
 DOING TWO, ONE ON EACH SIDE. WOULD YOU PLEASE REFER TO
 THE FOLLOWING 2020 FBC R P3005.2.3 BUILDING DRAIN AND
 BUILDING SEWER JUNCTION AND R3102.1 REQUIRED VENT
 EXTENSION, THE VENT SYSTEM SERVING EACH BUILDING DRAIN
 SHALL HAVE NOT LESS THAN ONE VENT PIPE; THAT EXTENDS TO
 THE OUTDOORS?
  
 2. ON SHEET P1.2;
 A. THERE IS A WATER FEATURE IN THE COURTYARD. WOULD YOU
 PLEASE PROVIDE A DETAIL AND BACKFLOW DEVICE BEING USED
 UNDER THE PLUMBING FIXTURE CONNECTION SCHEDULE ON PAGE
 P1.0 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3
 (12) RESIDENTIAL PLUMBING.
  
 B. THERE IS A BACKFLOW DEVICE AT THE METER THAT
 PROTECTS THE CITY OF WEST PALM BEACH WITH THEIR
 UTILITIES DEPARTMENT; CROSS CONNECTION PROGRAM MAY NEED
 TO BE A REDUCED PRINCIPAL VACUUM BREAKER. THE SECOND
 BACKFLOW IS A PRESSURE VACUUM BREAKER AT THE METER, BUT
 K COPPER IS NOT ALLOWED ON THE SIDE FROM THE METER TO
 THE DEVICE, ONLY L COPPER. WOULD YOU PLEASE CONTACT
 THEM TO DETERMINE WHAT THE NEEDED AT 561-822-2240?
  
 C. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 DEVICES PER THE WPB AMENDMENTS TO FBC SEC. 105.1.
  
 D. HOT WATER LINES UNDER SLAB NOT IN CONDITION SPACE
 NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020
 FBC SEC. RE 403.5.3. PLEASE PLACE A NOTE.
  
 E. IF THE TANKLESS HAS A CONDENSATE, IT NEEDS TO BE 1'
 AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC. R318.5.
  
 3. ON SHEET P1.4;
 A. ON THE ISOMETRIC FOR THE HOT WATER RECIRCULATING
 SYSTEM, THERE IS NO CONTINUOUS LOOP ON THE SYSTEM AS IT
 TEE?S OFF IN SEVERAL LOCATIONS. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. HOT WATER LINES OUTSIDE NOT IN CONDITION SPACE NEED
 TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC
 SEC. RE 403.5.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  