2021-09-23 13:31:16 | 09/23/21 1 ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. WOULD YOU PLEASE SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE |
| PER 2020 FBC RES. SECS. G2413.4.1, G2413.4.2. |
| |
| 2. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC RES. SEC. |
| G2413. |
| |
| 3. MOST TANKLESS UNITS CALL FOR A 10.5" WATER COLUMN, |
| AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| SEC. G2421.1. |
| |
| 4. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS |
| FOR ALL GAS EQUIPMENT PER THE WPB AMENDMENTS TO THE FBC |
| SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. WOULD YOU PLEASE SHOW ON PLANS THE LOCATION OF THE |
| TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF |
| ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATER? THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| HOUSE PLAN CAN BE HAND-DRAWN PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| 6. GAS UNITS MAY REQUIRE CONDENSATE, AND THEY NEED TO |
| BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC |
| R318.5. A NOTE ON ISO WILL BE OK. |
| |
| 7. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE |
| INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| 403.5.3. A NOTE ON ISO WILL BE OK. |
| |
| 8. THE GRILL SEEMS TO BE IN A COVERED PATIO; IF SO, |
| PLEASE PROVIDE THE MANUFACTURER'S RECOMMENDATION FOR A |
| VENTILATION HOOD PER THE 2020 FBC RES. SEC. G2408.1. |
| THE GRILL MAY REQUIRE A VENT IF IN THE CABINET. |
| |
| 9. WOULD YOU PLEASE LABEL AND SHOW ALL UNIONS IN FRONT |
| OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. |
| SEC G2421.2. |
| |
| 10. WOULD YOU PLEASE LABEL THE SHUTOFF VALVE ON GAS |
| ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC |
| RES. SEC. G2420.5. |
| |
| 11. THE SHUT-OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| GD, ACCESS. A NOTE ON ISO WILL BE OK. |
| |
| 12. DRIP LEG ON EQUIPMENT IS SHOWN INSTALLED |
| INCCORECTLY. WOULD YOU PLEASE REFER TO THE 2020 FBC R |
| FIGURE G2419.4 (408.4) METHOD OF INSTALLING A TEE |
| FITTING SEDIMENT TRAP |
| |
| 13. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020 |
| FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS). |
| |
| 14. IF USING LOVERS FOR COMBUSTION AIR, PLEASE SHOW THE |
| LOCATION OF THE LOUVERS THAT ARE BEING INSTALLED. THE |
| LOUVERS CANNOT BE LOCATED ON AN EXTERIOR WALL THAT IS |
| FIRE RATED AS THE FIRE RATING OF THE WALL MUST BE |
| MAINTAINED PER THE WPB AMENDMENTS TO FBC SEC.107.2.1. |
| |
| 15. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC |
| RES. SEC. G2413.2 AND G2404.3. |
| |
| 16. WOULD YOU PLEASE PROVIDE THE TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD USED IN THE DESIGN OF THIS SYSTEM PER |
| THE 2020 FBC RES. SEC. G2413.3. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |