2021-09-24 11:55:361ST REVIEW FBC-2020 RES. GAS
 PERMIT- 21090106
 9/24/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P3: PLEASE ADD THE LOW PRESSURE GAS PIPING
 SIZING TABLES FOR THE SCHEDULE 40 METALLIC AND THE
 CSST- SECTION G2413.4 FBC RES.
  
 2) P3: THE RISER SHOWS A FLOOR PENETRATION THAT APPEARS
 TO BE IN THE YARD AREA OF THE PROPERTY BASED ON THE
 FLOOR PLAN- PLEASE CORRECT OR CLARIFY WHAT FLOOR IS
 BEING PENETRATED- SECTION 107.2.1 WPB.
  
 3) P3: SHOW GAS TIGHT CAPS AT ALL FUTURE APPLIANCE
 TERMINATIONS- G2415.15 FBC RES.
  
 4) P3: INDICATE THE MAKES AND MODELS OF THE REGULATORS
 AND SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING THE
 SELECTED MODELS, THE INLET AND OUTLET PIPE SIZES AND
 PRESSURES- SECTION G2421.1 & G2421.2 FBC RES.
  
 5) P3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 RANGE AND PROVIDE COMBUSTION AIR CALCULATIONS- SECTIONS
 G2407.1 & G2447.1 FBC RES.'
  
 6) P3 & P4: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER AND SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL- SECTION G2448.1 FBC RES. PROVIDE
 AN INSTALLATION DETAIL ON THE PLAN INDICATING THE
 REQUIRED CLEARANCES TO BUILDING OPENINGS, GRADE, AND
 OVERHEAD CONSTRUCTION, AND PROVIDE CONDENSATE DISPOSAL
 DETAILS- SECTION G2448.1 FBC RES.
  
 7) P3: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE BBQ- SECTION G2447.1 FBC
 RES. PLEASE NOTE THAT MANY OF THE MANUFACTURER?S
 INSTALLATION GUIDELINES PROHIBIT INSTALLATION OF A BBQ
 GRILL UNDER OVERHEAD CONSTRUCTION AND HAVE RECOMMENDED
 CLEARANCES TO COMBUSTIBLES ETC. PROVIDE PLAN AND
 ELEVATION VIEWS OF THE GRILL SHOWING ALL REQUIRED
 CLEARANCES IN ACCORDANCE WITH THE MANUFACTURER'S
 GUIDELINES. PLEASE NOTE THAT AN EXHAUST HOOD AND DUCT
 MAY BE REQUIRED PER THE MANUFACTURER- G2447.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  