2022-02-17 11:19:32 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21090053 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| THIS REVIEW IS FOR THE MAIN HOUSE ONLY. COTTAGE PERMIT |
| NUMBER IS 22010888. THE CABANA WOULD BE CONSIDERED A |
| HABITABLE SPACE AND MUST BE CONDITIONED. PLEASE SUBMIT |
| MECHANICAL DRAWINGS FOR THIS CABANA. THE ELECTRICAL |
| SHEET CALLS FOR A MINI SPLIT, IF THIS IS TO BE USED FOR |
| THE CABANA PLEASE PROVIDE THE MECHANICAL EQUIPMENT |
| SIZING CALCULATIONS ALONG WITH THE MECHANICAL DRAWING. |
| |
| 1) THE SQUARE FOOTAGE SUBMITTED FOR THE MAIN HOUSE IN |
| THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT |
| SIZING CALCULATIONS DO NOT MATCH. PLEASE CORRECT THIS. |
| |
| 2) PLEASE PROVIDE DUCT SIZES ON DUCTS FROM AHU TO FIRST |
| FLOOR AND DUCT FROM AHU TO TRANSFER BOX ABOVE THE |
| MASTER BATH. FBC 107.2.1 |
| |
| 3) PLEASE PROVIDE A DETAIL OF THE ANCHORING OF THE |
| CONDENSING UNIT. FBC RES M1307.2 |
| |
| 4) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND |
| TERMINATION LOCATION. FBC RES M1411.3 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |