2021-10-07 20:52:52 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. MINIMUM GEC SIZE FOR COLD WATER PIPE IS #4 CU NOT |
| NUMBER #6. PROVIDE CORRECTION. NEC 250.66 |
| |
| 2. 100AMP PANEL FOR COTTAGE DOES NOT SHOW MAIN BREAKER. |
| MAIN BREAKER REQUIRED FOR SEPARATE STRUCTURE BECAUSE |
| THERE ARE MORE THAN 6 THROWS OF THE HAND. NEC 225.32 & |
| 225.33 |
| |
| 3. SEPARATE PERMIT IS REQUIRED FOR COTTAGE STRUCTURE. |
| FBC 105.1 |
| |
| 4. NOTE ON PLAN STATES AIC RATING WILL BE SUPPLIED BY |
| FINAL INSPECTION. THIS IS NOT PERMITTED. AIC RATING |
| WILL BE REQUIRED BEFORE PERMIT ISSUANCE. PROVIDE |
| CORRECTION |
| |
| PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| |
| 5. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| RE E3607.3 |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |