2021-10-07 20:52:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MINIMUM GEC SIZE FOR COLD WATER PIPE IS #4 CU NOT
 NUMBER #6. PROVIDE CORRECTION. NEC 250.66
  
 2. 100AMP PANEL FOR COTTAGE DOES NOT SHOW MAIN BREAKER.
 MAIN BREAKER REQUIRED FOR SEPARATE STRUCTURE BECAUSE
 THERE ARE MORE THAN 6 THROWS OF THE HAND. NEC 225.32 &
 225.33
  
 3. SEPARATE PERMIT IS REQUIRED FOR COTTAGE STRUCTURE.
 FBC 105.1
  
 4. NOTE ON PLAN STATES AIC RATING WILL BE SUPPLIED BY
 FINAL INSPECTION. THIS IS NOT PERMITTED. AIC RATING
 WILL BE REQUIRED BEFORE PERMIT ISSUANCE. PROVIDE
 CORRECTION
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 5. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.