2021-11-05 09:08:02 | BUILDING PLAN REVIEW |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE |
| CABANA/GARAGE STRUCTURE. |
| |
| 1. CORRECT GOVERNING CODES ON PAGE A1 TO 2020FBC 7TH |
| ED. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 2. PROVIDE A COPY OF THE BOUNDRY LINE SURVEY. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 3. PROVIDE SETBACK DEMENSIONS TO SITE PLAN. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 4. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 |
| IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED BOUNDARY LINE SURVEY. |
| FBC R401.3 SITE DRAINAGE |
| |
| 5. PLACE EXT. WALL INSULATION TYPE AND R VALUE ON PLAN. |
| 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| 107.2.5. |
| |
| 6. PROVIDE AN ENERGY SUBMITTAL. |
| FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| STORIES. |
| FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE |
| ALTERNATIVE. |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| 7. PROVIDE A ROOF FRAMING PLAN. |
| 7A) .PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER |
| FIGURE R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES |
| R301.2.1.1WIND DESIGN REQUIRED. |
| 7B) .PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER |
| DESIGN PRESSURES. |
| TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING |
| SCHEDULE FOR WOOD STRUCTURAL PANELS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| PLEASE UPLOAD YOUR DOCUMENTS TO PROJECT DOX. DO NOT |
| E-MAIL DOCUMENTS TO THE PLANS EXAMINER. |
| |
| PLAN REVIEW COMMENTS: |
| YOU CAN CHECK THE STATUS OF YOUR SUBMITTAL AND VIEW THE |
| PLAN REVIEW COMMENTS BY FOLLOWING THE INSTRUCTIONS |
| BELOW: |
| COPY AND PASTE THE FOLLOWING LINK INTO ANY INTERNET |
| BROWSER. |
| |
| HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| US.ASPX |
| |
| OPEN THE ONESTOPSHOP WEB-SITE FOR PERMIT STATUS |
| |
| ? ENTER IN THE PERMIT NUMBER ? SELECT SEARCH |
| ? LEFT CLICK ON PERMIT NUMBER |
| ? UNDER PERMIT INFORMATION SELECT PLAN REVIEWS TAB |
| ? ANY OPEN REVIEW STOP MEANS THAT REVIEW IS STILL |
| PENDING. |
| ? CLICK ON THE LATEST REVIEW NAME AND NUMBER TO REVIEW |
| COMMENTS. |
| |
| |
| |