2021-09-10 18:09:58 | RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21090021 |
| |
| NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| SHALL COMPLY WITH THE MATERIALS AND METHODS |
| REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| |
| 1- PROVIDE COMPLETE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR LOW SLOPE ROOF (FLAT ROOF). THIS WAS |
| REQUESTED ON PREVIOUS REVIEW BUT IT WAS NOT SUBMITTED. |
| NOTE: CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO |
| BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T MEET THE |
| DESIGN PRESSURES FOR ALL ROOF ZONES AS REQUIRED BY SEC. |
| R301..2.1 FBC-RESIDENTIAL, THEN SIGNED AND SEALED RAS |
| 117 CALCULATIONS MAY BE REQUIRED. RAS 117 CALCULATIONS |
| NEED TO BE SITE SPECIFIC. CALCULATIONS SUBMITTED ARE |
| FOR ANOTHER JOB: 639 S MANGONIA CIRCLE. ALSO, |
| CALCULATIONS NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND |
| SIGNATURE. EITHER SUBMITTED ELECTRONICALLY WITH A |
| DIGITAL SIGNATURE OR HARD COPY WITH ENGINEER'S ORIGINAL |
| SEAL/SIGNATURE. |
| |
| 2- PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH |
| THE NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. |
| SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |
| ******************************************************* |
| ******************************************************* |
| ************************************************** |
| ORIGINAL COMMENTS: |
| |
| PLAN REVIEW ROOFING |
| |
| CHRISTOPHER S. THROOP, C.B.O., CFM |
| PLANS EXAMINER II PX3169/SFP306 |
| INSPECTOR BN4338 |
| BUILDING OFFICIAL BU1635 |
| ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| DEVELOPMENT SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| 2017 NEC |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| REF: CONTRACT. SOW INCLUDES PITCHED ROOF (SHINGLES) AND |
| FLAT ROOF. |
| |
| 1. PROVIDE PRODUCT APPROVALS FOR FLAT ROOF. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 2. PROVIDE PRODUCT APPROVALS (IF REQUIRED) FOR APPROVED |
| UNDERLAYMENTS. |
| FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |