Plan Review Notes For Permit 21090020 |
Permit Number |
21090020 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-01 11:18:29 | ELECTRICAL REVIEW FAILED | | 1) WALL HUNG FOUNTAIN REQUIRES GFCI PROTECTION AS PER | | NEC 680.51(A) | | 2) EXTENSION CORDS USED AS DESCRIBED IN NOTE (9) ON | | SHEET E01 ARE NOT NEC COMPLIANT, NEC 400.12(1). PLEASE | | PROVIDE A PERMANENT NEC COMPLIANT WIRING METHOD. | | 3) LOW VOLTAGE WIRING WILL REQUIRE A SEPARATE PERMIT AS | | PER WEST PALM BEACH BUILDING DEPARTMENT POLICY | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|