2022-02-01 11:18:29ELECTRICAL REVIEW FAILED
 1) WALL HUNG FOUNTAIN REQUIRES GFCI PROTECTION AS PER
 NEC 680.51(A)
 2) EXTENSION CORDS USED AS DESCRIBED IN NOTE (9) ON
 SHEET E01 ARE NOT NEC COMPLIANT, NEC 400.12(1). PLEASE
 PROVIDE A PERMANENT NEC COMPLIANT WIRING METHOD.
 3) LOW VOLTAGE WIRING WILL REQUIRE A SEPARATE PERMIT AS
 PER WEST PALM BEACH BUILDING DEPARTMENT POLICY
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  